7.2Details of protective function
7-19
Error No.
Protective function
Causes
Measures
Main
Sub
70
0
U-phase current detector
error protection
In the driver module, each axis motor
U-phase current detection offset value has
some error.
Turn off power once, and turn on again.
Even so, if an error indication appears and
an error occurs, failure is possible.
Discontinue the use and replace the motor
and driver module.
Return to a dealer for investigation (repair).
1
W-phase current detector
error protection
In the driver module, each axis motor
W-phase current detection offset value has
some error.
72
0
Thermal error protection
Thermal has some error.
80
0
ESM unauthorized
request error protection
In the EtherCAT communication of the
driver module, the change state request
which cannot change from the present state
was received.
Init
to SafeOP
Init
to OP
PreOP to OP
OP
to Bootstrap
PreOP to Bootstrap
SafeOP to Bootstrap
Check the change state request of host
controller.
1
ESM undefined request
error protection
In the EtherCAT communication of the
driver module, the change state request
which does not have a definition (except the
following) was received.
1 : Request Init State
2 : Request Pre-Operational State
3 : Request Bootstrap State
4 : Request Safe-Operational State
8 : Request Operational State
Check the change state request of host
controller.
2
Bootstrap requests error
protection
In the EtherCAT communication of the
driver module, the following change state
request was received.
3 : Request Bootstrap State
Check the change state request of host
controller.
3
Incomplete PLL error
protection
In the EtherCAT communication of the
driver module, phasing servo and
communication (PLL lock) could not be
completed even after the lapse of 1s after
the start of the synchronization process.
<In case of DC>
Check setting of DC mode.
It is checked whether propagation delay
compensation or drift compensation is
correct.
<In case of SM2>
It is checked whether the transmitting
timing of PDO from host controller is
constant.
Check whether there is any problem in
wiring of the EtherCAT communication
cable.
Check whether there is excessive noise
on the EtherCAT communication cable.
4
PDO watchdog error
protection
In the EtherCAT communication of the
driver module, during PDO communication
(SafeOP or OP state), bit10 of AL Event
Request(0220h) did not turn on within the
time is set ESC register addresses 0400h
and 0420h.
Check whether the transmitting timing of
PDO from host controller is constant (not
stop).
Increase the timeout value of the PDO
watchdog detection.
Check whether there is any problem in
wiring of the EtherCAT communication
cable.
Check whether there is excessive noise
on the EtherCAT communication cable.
(To be continued)
Summary of Contents for MINAS A6 Series
Page 10: ...Table of contents x Blank page...
Page 11: ...1 Introduction...
Page 26: ...Introduction 1 16 Blank page...
Page 27: ...2 Interface Specifications...
Page 46: ...Interface Specifications 2 20 Blank page...
Page 47: ...3 Front Panel Specifications...
Page 57: ...4 Basic Functions...
Page 85: ...5 Auto Tuning Functions...
Page 151: ...6 Application Functions...
Page 185: ...7 Protective Functions...
Page 224: ...Protective Functions 7 40 Blank page...
Page 225: ...8 Advanced Safety Functions...
Page 230: ...Advanced Safety Functions 8 6 When test pulse is used Duplex safety input Safety input...
Page 245: ...9 List of Parameters...
Page 281: ...10 Timing Chart...
Page 290: ...Timing Chart 10 10 Blank page...
Page 291: ...11 Power Supply Module...