Application Functions
6-6
6.3.6 Fall prevention function in the event of alarms/servo-ON
6.3.6.1 Fall prevention function in the event of alarms
If the alarm requiring emergency stop has occurred, falling of the robot arm is prevented by maintaining the
energization to the motor until the external brake is actually operated after the brake release output
(BRK-OFF) is turned OFF.
This function can prevent a fall when alarm occurs by setting the sequence at alarm to emergency stop. This
function cannot be used for alarm that does not support emergency stop.
For details of Sequence at alarm, refer to Section "6.3.4 Sequence at alarm" and "6.3.5 Emergency stop
upon occurrence of alarm".
For details of the alarm that supports emergency stop, refer to Section "7.1 List of protective function".
To release the brake from the I/O connector, refer to "2.4 I/O signal allocation function".
To release the brake from the exclusive output for holding brake, refer to "2.5 Mechanical brake output".
Relevant parameters
Relevant parameters
Class No. Attribute Title
Range
Unit
Function
5
10
B
Sequence at alarm 0 to 7
-
Specify the status during deceleration and after stop, after
occurrence of alarm.
Setting the parameter to one of 4 to 7, enables emergency stop.
6
10
B
Function
expansion setup
-32768 to
32767
-
Set the bit related to the fall prevention function.
bit10: Fall prevention function in case of alarms
0: Invalid
1: Valid
To enable the fall prevention function, normally set this
parameter to 1.
The least significant bit is bit0.
6
51
B
Wait time for
emergency stop
0 to
10000
ms
Set the time to maintain the motor energization after the brake
release output (BRK-OFF) is turned OFF in the event of an alarm
requiring emergency stop.
When the set value is 0, the fall prevention function is disabled.
This parameter is enabled even when Pr6.10 "Function expansion
setup" is not set to bit10=1. To enable the fall prevention function,
however, be sure to set Pr6.10 "Function expansion setup" to
bit10=1.
Contents
Operation of the fall prevention function in the event of the alarm requiring emergency stop
Summary of Contents for MINAS A6 Series
Page 10: ...Table of contents x Blank page...
Page 11: ...1 Introduction...
Page 26: ...Introduction 1 16 Blank page...
Page 27: ...2 Interface Specifications...
Page 46: ...Interface Specifications 2 20 Blank page...
Page 47: ...3 Front Panel Specifications...
Page 57: ...4 Basic Functions...
Page 85: ...5 Auto Tuning Functions...
Page 151: ...6 Application Functions...
Page 185: ...7 Protective Functions...
Page 224: ...Protective Functions 7 40 Blank page...
Page 225: ...8 Advanced Safety Functions...
Page 230: ...Advanced Safety Functions 8 6 When test pulse is used Duplex safety input Safety input...
Page 245: ...9 List of Parameters...
Page 281: ...10 Timing Chart...
Page 290: ...Timing Chart 10 10 Blank page...
Page 291: ...11 Power Supply Module...