6.8Deterioration diagnosis warning function
6-25
Deterioration diagnosis warning for constant velocity torque command average value
Deterioration diagnosis velocity output (V-DIAG) is ON when the motor velocity is within the range of Pr4.35
"Speed coincidence range" of Pr5.75 "Deterioration diagnosis velocity setting".
When deterioration diagnosis velocity output (V-DIAG) is turned ON, torque command average calculation
will start and after lapse of the set time of Pr5.76, deterioration diagnosis judgment by torque command
average will become effective. This will continue while deterioration diagnosis velocity output (V-DIAG)
remains output ON, however will return to invalid condition when the output is turned OFF.
The upper limit and lower limit values for torque command average can be set by parameters Pr5.77 and
5.78 respectively. Deterioration diagnostic warning WngAC is generated in case these upper or lower limit
values have been exceeded for changes in the load characteristic estimates.
When a deterioration diagnosis warning does not occur for the torque command average value
When a deterioration diagnosis warning occurs for the torque command average value
Summary of Contents for MINAS A6 Series
Page 10: ...Table of contents x Blank page...
Page 11: ...1 Introduction...
Page 26: ...Introduction 1 16 Blank page...
Page 27: ...2 Interface Specifications...
Page 46: ...Interface Specifications 2 20 Blank page...
Page 47: ...3 Front Panel Specifications...
Page 57: ...4 Basic Functions...
Page 85: ...5 Auto Tuning Functions...
Page 151: ...6 Application Functions...
Page 185: ...7 Protective Functions...
Page 224: ...Protective Functions 7 40 Blank page...
Page 225: ...8 Advanced Safety Functions...
Page 230: ...Advanced Safety Functions 8 6 When test pulse is used Duplex safety input Safety input...
Page 245: ...9 List of Parameters...
Page 281: ...10 Timing Chart...
Page 290: ...Timing Chart 10 10 Blank page...
Page 291: ...11 Power Supply Module...