7.3Warning function
7-33
Class No.
Attribute
(Note 1)
Title
Range
Unit Function
6
96
A
Over-load warning
release level
0 to 114
%
Sets the threshold value for releasing the warning when
the load factor decreases from the state when the
overload warning is occurring.
Sets with the overload load factor.
If 0 is set, overload warning detection is performed under
conventional conditions (85% of overload protection
level).
In addition, if other than "Pr6.96 <= Pr6.95 < (Overload
protection level)" is set, overload warning detection is
performed under conventional conditions (85% of
overload protection level).
6
97
B
Function
expansion setup 3
-2147483648
to
2147483647
-
bit 1: Deterioration diagnosis warning function
0:Invalid
1:valid
7
14
C
Main power off
warning detection
time
0 to 2000
1 ms
Specifies a time to wait until a main power off warning is
detected when main power shut-off continues.:
0 to 9, 2000:
10 to 1999:
Warning detection is disabled.
Unit is [ms]
PSM
Pr.
Name
Setting
range
Shipping
setting
Unit Content
03
Main power off warning
detection time
0 to 2000 40
ms
Sets the main power off warning detection time. The main
power off warning is not detected when the setting value is
smaller than 10 or is set to 2000.
Summary of Contents for MINAS A6 Series
Page 10: ...Table of contents x Blank page...
Page 11: ...1 Introduction...
Page 26: ...Introduction 1 16 Blank page...
Page 27: ...2 Interface Specifications...
Page 46: ...Interface Specifications 2 20 Blank page...
Page 47: ...3 Front Panel Specifications...
Page 57: ...4 Basic Functions...
Page 85: ...5 Auto Tuning Functions...
Page 151: ...6 Application Functions...
Page 185: ...7 Protective Functions...
Page 224: ...Protective Functions 7 40 Blank page...
Page 225: ...8 Advanced Safety Functions...
Page 230: ...Advanced Safety Functions 8 6 When test pulse is used Duplex safety input Safety input...
Page 245: ...9 List of Parameters...
Page 281: ...10 Timing Chart...
Page 290: ...Timing Chart 10 10 Blank page...
Page 291: ...11 Power Supply Module...