5.2Manual adjusting function
5-39
Relevant parameters
Set up damping control operation using the parameters shown below.
Relevant parameters
Class No. Attribute
Title
Range
Unit
Function
2
13
B
Selection of
damping filter
switching
0 to 6
-
Among 4 filters select the filters to be used for damping control.
Setup value is 0:
Up to 2 filters can be used simultaneously.
Setup value is 1 or 2:
Reserved for manufacturer's use (do not set this)
Setup value 3:
Select the filter with command direction.
Pr2.13
Position
command
direction
Damping
1st
2nd
3rd
4th
0
-
Enabled
Enabled
Disabled Disabled
3
Positive
direction
Enabled
Disabled Enabled
Disabled
Negative
direction
Disabled Enabled
Disabled Enabled
Setting values 4 to 6:
Setting values 4 to 6 can be used only when position control
and 2-DOF control mode are disabled. Do not set when
full-closed control or 2-degree-of-freedom control mode is
enabled.
Pr2.13
Position
command
direction
Damping
1st
2nd
3rd
4th
4
-
Enabled
Enabled
Enabled
Disabled
5, 6
-
Same as Pr2.13=0
(1) Switching between the damping frequency and damping filter setting is performed at the rising edge of the
command that causes the number of command pluses per command detection period (0.125 ms) (at
upstream of position command filter) changes from 0 to any other value while the positioning complete is
being output.
Even if the control mode is changed to position control after changing the damping frequency and
damping filter settings during velocity control or torque control, the setting is not changed.
Especially, at higher damping frequency, or if it becomes disabled, and wider positioning complete range
is set up, and if large pulse (area is equivalent of time integration of the value of position command at
upstream of the filter minus the value of position command at downstream of filter) remains in the filter
during switching, it is rapidly discharged upon switching and returns to original position, and the motor will
move at a speed higher than normal command velocity.
(2) There is delay from setting change of damping frequency or damping filter to internal computation and
application of new setting values. If the switching described in (1) occurs during this delay time,
application of new value will be suspended.
Summary of Contents for MINAS A6 Series
Page 10: ...Table of contents x Blank page...
Page 11: ...1 Introduction...
Page 26: ...Introduction 1 16 Blank page...
Page 27: ...2 Interface Specifications...
Page 46: ...Interface Specifications 2 20 Blank page...
Page 47: ...3 Front Panel Specifications...
Page 57: ...4 Basic Functions...
Page 85: ...5 Auto Tuning Functions...
Page 151: ...6 Application Functions...
Page 185: ...7 Protective Functions...
Page 224: ...Protective Functions 7 40 Blank page...
Page 225: ...8 Advanced Safety Functions...
Page 230: ...Advanced Safety Functions 8 6 When test pulse is used Duplex safety input Safety input...
Page 245: ...9 List of Parameters...
Page 281: ...10 Timing Chart...
Page 290: ...Timing Chart 10 10 Blank page...
Page 291: ...11 Power Supply Module...