5.2Manual adjusting function
5-57
How to use
Adjust the load change inhibit function using the disturbance suppression setup by reference to Section
"5.2.10 Load variation suppression function", and measure quadrant projection.
Level is unsatisfactory, conduct further fine adjustment using quadrant projection suppression function.
1. Reclose control power supply after enabling quadrant projection suppression function (Pr
6.47 bit14 = 1)
2. Set initial values to: Pr 5.47 = 0, Pr 5.48 = Pr 1.04, Pr 5.49 =0.
3. Measure the magnitude of quadrant projection and conduct fine adjustments to Pr 5.45 and
Pr 5.46 of each axis.
-
When quadrant projection is delayed from the timing of the movement direction is
reversed, try changing Pr 5.47 and Pr 5.48.
-
To set the compensation amount of quadrant projection by inversion direction when the
direction of the velocity has changed, set Pr6.97 bit0 to 1 and try change Pr5.49.
Summary of Contents for MINAS A6 Series
Page 10: ...Table of contents x Blank page...
Page 11: ...1 Introduction...
Page 26: ...Introduction 1 16 Blank page...
Page 27: ...2 Interface Specifications...
Page 46: ...Interface Specifications 2 20 Blank page...
Page 47: ...3 Front Panel Specifications...
Page 57: ...4 Basic Functions...
Page 85: ...5 Auto Tuning Functions...
Page 151: ...6 Application Functions...
Page 185: ...7 Protective Functions...
Page 224: ...Protective Functions 7 40 Blank page...
Page 225: ...8 Advanced Safety Functions...
Page 230: ...Advanced Safety Functions 8 6 When test pulse is used Duplex safety input Safety input...
Page 245: ...9 List of Parameters...
Page 281: ...10 Timing Chart...
Page 290: ...Timing Chart 10 10 Blank page...
Page 291: ...11 Power Supply Module...