Timing Chart
10-8
*4 We recommend the setting in which Pr4.38 (Mechanical brake action at running setup) becomes equal toPr6.14 (Emergency stop
time at alarm). If Pr4.38 is set to less than or equal to Pr6.14, the brake operates after the length of time set for Pr4.38 elapses. If
Pr4.38 is set to greater than Pr6.14, the brake does not operate after the length of time set for Pr4.38 elapses,but the brake operates
at the time of transition to non-energizing.
*5 The mechanical brake does not follow the brake release output (BRK-OFF) but operates at the timing when the mechanical brake
detects an error, when Err17.0 "Mechanical brake circuit overvoltage protection" or Err17.1 "Mechanical brake circuit overload
protection" occurs while a mechanical brake circuit with a built-in driver is used.
For details about mechanical brake circuit, refer to "REFERENCE SPECIFICATIONS Driver module section (SX-DSV03454)".
Summary of Contents for MINAS A6 Series
Page 10: ...Table of contents x Blank page...
Page 11: ...1 Introduction...
Page 26: ...Introduction 1 16 Blank page...
Page 27: ...2 Interface Specifications...
Page 46: ...Interface Specifications 2 20 Blank page...
Page 47: ...3 Front Panel Specifications...
Page 57: ...4 Basic Functions...
Page 85: ...5 Auto Tuning Functions...
Page 151: ...6 Application Functions...
Page 185: ...7 Protective Functions...
Page 224: ...Protective Functions 7 40 Blank page...
Page 225: ...8 Advanced Safety Functions...
Page 230: ...Advanced Safety Functions 8 6 When test pulse is used Duplex safety input Safety input...
Page 245: ...9 List of Parameters...
Page 281: ...10 Timing Chart...
Page 290: ...Timing Chart 10 10 Blank page...
Page 291: ...11 Power Supply Module...