11.5Protective functions
11-11
11.5.2 Details of protective functions
PSM
alarm
number
PSM alarm name
Cause of alarm
Measures of alarm
01
PSM control power
supply undervoltage
alarm
The control power voltage of the power supply
module has dropped to below the specified
value.
Supply the correct voltage to the control power
input (DC 24 V).
1)
The control power supply voltage (DC24V)
is low:
The occurrence of an instantaneous
power failure, etc.
1) Measure the voltage at the control power
input connector and check if it is the
specified value:
Check that the control power is not turned
on or off at an extreme slow up / slow
down.
2)
Insufficient control power capacity:
The power supply voltage has dropped
due to the inrush current when the control
power is turned on.
2) Increase the control power capacity:
Try changing the control power.
3)
Power supply module failure:
Related circuit is broken
3) Replace the power supply module.
02
PSM main power supply
overvoltage alarm
The main power supply DC bus voltage
exceeded the allowable input voltage range.
Supply the correct voltage to the main power
input (AC400V).
In addition, an instantaneous voltage increase
due to regenerative power from the driver
module is avoided.
1)
The voltage of the converter section
exceeded the specified value.
1) Measure the line voltage of the connectors
X102 terminal (L1, L2, L3) and check for
abnormal voltage fluctuations.
2)
Voltage jumps with phase-advancing
capacitors and UPS (Uninterruptible
Power Supply).
2) Try removing the phase advance capacitor
and UPS.
3)
Disconnection of external regenerative
resistor.
3) Measure the resistance value of the
external regenerative resistor with a tester.
If it is infinity, it is broken. Replace the
external resistor.
4)
External regenerative resistance is
inappropriate and regenerative energy
cannot be absorbed.
4) Change to the specified regenerative
resistance and power value.
5)
Power supply module failure:
Related circuit is broken
5) Replace the power supply module.
05
PSM main power supply
open phase alarm
A phase failure of the main power supply
connector X102 terminal (L1, L2, L3) was
detected in the main power established state.
Connect the correct power supply to the main
power input (AC400V).
1)
Disconnection or drop out of L1, L2, and
L3 lines.
1) Check the main power input wiring.
2)
L1-L2 / L2-L3 / L1-L3 Interphase voltage
imbalance.
2) Measure the line voltage of the main power
input connector (L1, L2, L3). Eliminate
phase voltage imbalance.
3)
The main power supply voltage is low.
3) Check if the line voltage is the specified
value.
4)
Power supply module failure:
Related circuit is broken
4) Replace the power supply module.
(To be continued)
Summary of Contents for MINAS A6 Series
Page 10: ...Table of contents x Blank page...
Page 11: ...1 Introduction...
Page 26: ...Introduction 1 16 Blank page...
Page 27: ...2 Interface Specifications...
Page 46: ...Interface Specifications 2 20 Blank page...
Page 47: ...3 Front Panel Specifications...
Page 57: ...4 Basic Functions...
Page 85: ...5 Auto Tuning Functions...
Page 151: ...6 Application Functions...
Page 185: ...7 Protective Functions...
Page 224: ...Protective Functions 7 40 Blank page...
Page 225: ...8 Advanced Safety Functions...
Page 230: ...Advanced Safety Functions 8 6 When test pulse is used Duplex safety input Safety input...
Page 245: ...9 List of Parameters...
Page 281: ...10 Timing Chart...
Page 290: ...Timing Chart 10 10 Blank page...
Page 291: ...11 Power Supply Module...