Wiring
46
FQ2-S4 User’s Manual
RS-232C Interface Sensor Data Unit (FQ-SDU2
@
)
For the I/O connector harness, use an FQ-VP2
@@@
Parallel Cable for the FQ-SDU2 or a MIL-standard
harness, such as the OMRON XZ2F. (The Cables are sold separately.)
Signal
Application
Power supply (24 V)
These terminals are for the external power supply (24 V).
• Wire the power supply separately from other devices. If the wiring for other devices is
placed together or in the same duct as the wiring for the Vision Sensor, the influence
of electromagnetic induction may cause the Sensor to malfunction or may damage it.
• Do not allow the load current to exceed 50 mA. The output circuit may be damaged if
the load current exceeds 50 mA.
Power supply (0 V)
Frame ground
This is the frame ground terminal. Connect it to the ground wire.
FQ2-S4 (Sensors with Built-in Lighting or
Sensors with C-mounts)
Power supply (24 V)
Power supply (0 V)
Frame ground
RS-232C connector
1
2
17
18
3
4
19
20
5
6
21
22
7
8
23
24
9
10
25
26
11
12
27
28
13
14
29
30
15
16
31
32
(Screw size: M3,
Tightening torque:
0.54 N·m)
FQ-WU0
@@
Sensor Data Unit Cable
Important
Summary of Contents for FQ2-S4
Page 1: ...User s Manual Smart Camera FQ2 S4 Cat No Z330 E1 01 ...
Page 58: ...Setting Up Ethernet 56 FQ2 S4 User s Manual MEMO ...
Page 214: ...Calculations and Judgements Using Inspection Item Data 212 FQ2 S4 User s Manual MEMO ...
Page 234: ...Adjusting Judgement Parameters during Operation 232 FQ2 S4 User s Manual MEMO ...
Page 458: ...Basic Troubleshooting 456 FQ2 S4 User s Manual MEMO ...
Page 591: ...Index FQ2 S4 User s Manual 589 Index 12 ...
Page 593: ......