PLC Link Connections
386
FQ2-S4 User’s Manual
●
Response Area
Vision Sensor (Slave) to PLC (Master)
First
word
Bits
Contents
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
+0
ERR Resv Resv Resv Resv Resv Resv Resv Resv Resv Resv Resv Resv READY BUSY FLG Control
signals
(32 bits)
+1
Resv Resv Resv Resv Resv Resv Resv Resv Resv Resv Resv Resv Resv
Resv
Resv GATE
+2
Command code
Com-
mand
code (32
bits)
+3
+4
Response code
Response
code (32
bits)
+5
+6
Response data
Response
data (32
bits)
+7
Signal
Signal name
Function
Application
FLG
Control Command Com-
pleted
This signal turns ON when the Vision Sensor
completes execution of the control command.
Command/
response commu-
nications
This signal automatically turns OFF when the
Control Command Execution Bit (EXE) signal
from the PLC turns OFF.
This signal turns ON after the control com-
mand code, response code, and response data
have been stored.
BUSY
Command Execution
Active
This signal is ON while the Vision Sensor is
executing a control command.
It is OFF while the Vision Sensor is not execut-
ing a control command.
READY
Ready
This signal turns ON when the Vision Sensor
can execute a command.
Command/
response commu-
nications
This signal turns OFF when the Vision Sensor
cannot execute a command.
ERR
Error
This signal turns ON when an error is detected
in the Vision Sensor.
This flag turns ON when an error occurs in
PLC link communications. This signal will
remain OFF for any errors other than PLC Link
communications errors.
Command/
response commu-
nications
This signal turns OFF when the Clear Error
(ERRCLR) signal from the PLC turns ON.
GATE
Data Output Completed
This signal turns ON when the Vision Sensor
finishes outputting data.
Data output after
measurements
If handshaking is enabled, the GATE signal
turns OFF automatically when you turn OFF
the Data Output Request (DSA) signal from the
PLC.
Important
Summary of Contents for FQ2-S4
Page 1: ...User s Manual Smart Camera FQ2 S4 Cat No Z330 E1 01 ...
Page 58: ...Setting Up Ethernet 56 FQ2 S4 User s Manual MEMO ...
Page 214: ...Calculations and Judgements Using Inspection Item Data 212 FQ2 S4 User s Manual MEMO ...
Page 234: ...Adjusting Judgement Parameters during Operation 232 FQ2 S4 User s Manual MEMO ...
Page 458: ...Basic Troubleshooting 456 FQ2 S4 User s Manual MEMO ...
Page 591: ...Index FQ2 S4 User s Manual 589 Index 12 ...