Controlling Operation and Outputting Data with the Sensor's Standard Parallel Connection
FQ2-S4 User’s Manual
297
8
Controll
ing
Ope
rati
on a
nd Outputting
Data
wi
th
a
Para
llel
Co
nne
ctio
n
Turning the ERROR Signal OFF
The ERROR signal turns ON when an error occurs.
After removing the cause of the error, turn the ERROR signal OFF using one of the following methods.
Method 1: Input an error clear command from an external device such as a PLC.
Method 2: Input a measurement trigger again.
(For example, turn the TRIG signal ON during a one-shot measurement.)
The ERROR signal will turn OFF when measurement is executed correctly.
Settings
[In/Out]
−
[I/O setting]
−
[I/O setting]
−
[Input]
−
[Input mode]
Press [Expand mode].
Wiring
Timing Chart
This function can be used in Run Mode only.
Color
Signal
State
Description
The signals shown at the left
are used.
Refer to the following
information for signal wiring.
Gray
IN0
OFF
Command parameter for clearing errors
Green
IN1
OFF
Red
IN2
ON
White
IN3
OFF
Purple
IN4
OFF
Yellow
IN5
ON
Command input for clearing errors
Orange
OUT1 (BUSY)
--
Processing in progress (default)
Light blue
OUT2 (ERROR)
--
ERROR signal (default)
1 Turn OFF IN0 to IN1 and IN3 to IN4
and turn ON IN2.
2 Turn ON the IN5 signal while the
BUSY signal is OFF to clear the error.
Note
OFF
ON
OFF
ON
OFF
ON
ERROR signal
BUSY signal
IN5 signal
ON for 1 ms min.
Allow 5 ms min. and then
turn ON IN5.
IN0 to IN4 signals
Summary of Contents for FQ2-S4
Page 1: ...User s Manual Smart Camera FQ2 S4 Cat No Z330 E1 01 ...
Page 58: ...Setting Up Ethernet 56 FQ2 S4 User s Manual MEMO ...
Page 214: ...Calculations and Judgements Using Inspection Item Data 212 FQ2 S4 User s Manual MEMO ...
Page 234: ...Adjusting Judgement Parameters during Operation 232 FQ2 S4 User s Manual MEMO ...
Page 458: ...Basic Troubleshooting 456 FQ2 S4 User s Manual MEMO ...
Page 591: ...Index FQ2 S4 User s Manual 589 Index 12 ...
Page 593: ......