Output Signals
Input Signals
Signal
Function
RUN
This signal is ON while the Sensor is in Run Mode. It will be OFF in Setup Mode.
BUSY
This signal does not change while clearing the OR and D signals.
However, do not clear the OR and D signals while the BUSY signal is ON.
The command will not be executed correctly.
OR
If this signal was ON, it will be turned OFF.
D0 to D15
If these signals were ON, they will be turned OFF.
GATE
This signal does not change while clearing the OR and D signals.
However, do not clear the OR and D signals while the GATE signal is ON.
The command will not be executed correctly. Also, the D and GATE outputs may not function correctly.
ACK
When the command has been completed normally, this signal is turned ON for the time that is set for the ACK
output time.
Signal
Function
IN0
Turn OFF.
IN1
Turn ON.
IN2 to IN5
Turn OFF.
IN6
Turn ON.
IN7
This signal is the trigger for clearing the OR and D signals.
Set the IN0 to IN6 signals, wait for at least 5 ms, and then turn ON the IN7 signal.
Summary of Contents for FQ2-S4
Page 1: ...User s Manual Smart Camera FQ2 S4 Cat No Z330 E1 01 ...
Page 58: ...Setting Up Ethernet 56 FQ2 S4 User s Manual MEMO ...
Page 214: ...Calculations and Judgements Using Inspection Item Data 212 FQ2 S4 User s Manual MEMO ...
Page 234: ...Adjusting Judgement Parameters during Operation 232 FQ2 S4 User s Manual MEMO ...
Page 458: ...Basic Troubleshooting 456 FQ2 S4 User s Manual MEMO ...
Page 591: ...Index FQ2 S4 User s Manual 589 Index 12 ...
Page 593: ......