Controlling Operation and Outputting Data with the Sensor's Standard Parallel Connection
FQ2-S4 User’s Manual
285
8
Controll
ing
Ope
rati
on a
nd Outputting
Data
wi
th
a
Para
llel
Co
nne
ctio
n
Sample Ladder Program
The following sample program is used to input a IN5 signal to perform continuous measurements. Continuous
measurements will be started when W0.00 turns ON and stopped when W0.01 turns ON.
• I/O Signal Allocations
Signal
Address
Output signals
OUT1 (BUSY signal)
CIO 0.01
Input signals
IN0
CIO 1.08
IN1
CIO 1.09
IN2
CIO 1.10
IN3
CIO 1.11
IN4
CIO 1.12
IN5
CIO 1.15
MOV
#0000
Q:1
W0.00
0000
#5
TMHH
SET
IN5
T0000
OUT1
W0.00
RSET
W0.00
RSET
IN5
W0.01
RSET
W0.00
Continuous
measurement
command bit
Continuous
measurement
command bit
BUSY signal
Continuous
measurement
stop bit
When the continuous measurement command
bit (W0.00) turns ON, the command
parameter for continuous measurements
(00000) is output to Q:1 (IN0 to IN4).
If the BUSY signal is OFF 5 ms after the
command parameter is output, the command
input for continuous measurements (IN5) is
turned ON and continuous measurements start
When the continuous measurement stop bit
(W0.01) turns ON, the command input for
continuous measurements (IN5) is turned
OFF and continuous measurements stop.
Summary of Contents for FQ2-S4
Page 1: ...User s Manual Smart Camera FQ2 S4 Cat No Z330 E1 01 ...
Page 58: ...Setting Up Ethernet 56 FQ2 S4 User s Manual MEMO ...
Page 214: ...Calculations and Judgements Using Inspection Item Data 212 FQ2 S4 User s Manual MEMO ...
Page 234: ...Adjusting Judgement Parameters during Operation 232 FQ2 S4 User s Manual MEMO ...
Page 458: ...Basic Troubleshooting 456 FQ2 S4 User s Manual MEMO ...
Page 591: ...Index FQ2 S4 User s Manual 589 Index 12 ...
Page 593: ......