YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
663
Terminal V1 will output an analog signal = 100% of the parameter set in
F4-01
.
4. View the monitor connected to terminal V1 and adjust
F4-05
.
•
Use Gain and Bias to Adjust the Output Signal Level of Terminal V2
You must stop the drive to adjust the output signal. Use this procedure to calibrate the drive:
1. View the
F4-04 [Terminal V2 Gain]
value on the keypad.
Terminal V2 will output a voltage = 100% of the monitor set in
F4-03 [Terminal V2 Function Selection]
.
2. View the monitor connected to terminal V2 and adjust
F4-04
.
3. View the
F4-06 [Terminal V2 Bias]
value on the keypad.
The analog signal equal to 0% of the parameter being set in
F4-03
will be output from terminal V2.
4. View the monitor connected to terminal V2 and adjust
F4-06
.
■
F4-01: Terminal V1 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
F4-01
(0391)
Terminal V1 Function
Selection
Sets the monitor signal output from terminal V1.
102
(000 - 999)
Set the
x-xx
part of the
Ux-xx [Monitors]
to set monitor data to output from the option card. For example, set
F4-
01 = 102
to monitor
U1-02 [Output Frequency]
.
Note:
•
You cannot use all of the monitors in all of the control methods.
•
When you use the terminal in through mode, set this parameter to
000
or
031
. You can use MEMOBUS/Modbus communications or
the communication option to set the terminal V1 output level from the PLC.
■
F4-02: Terminal V1 Gain
No.
(Hex.)
Name
Description
Default
(Range)
F4-02
(0392)
RUN
Terminal V1 Gain
Sets the gain of the monitor signal that is sent from terminal V1. Sets the analog signal output
level from the terminal V1 at 10 Vor 20 mA as 100% when an output for monitoring items is
100%.
100.0%
(-999.9 - +999.9%)
The maximum output voltage output from terminal V1 is ±10 V. Use
F4-07 [Terminal V1 Signal Level]
to set the
signal level.
Example settings:
When you use these settings, and the monitored output voltage is at 100% (drive rated current), the output voltage
of terminal V1 is 5 V (50% of 10 V). The output current is 200% of the drive rated current when terminal V1
outputs a maximum voltage of 10 V.
•
F4-01 [Terminal V1 Function Selection] = 102 (U1-02: Output Frequency)
•
F4-02 = 50.0%
•
F4-05 [Terminal V1 Bias] = 0.0%
•
F4-07 = 0 (0 V to 10 V)
■
F4-03: Terminal V2 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
F4-03
(0393)
Terminal V2 Function
Selection
Sets the monitor signal output from terminal V2.
103
(000 - 999)
Set the x-xx part of the
Ux-xx [Monitors]
to set monitor data to output from the option card. For example, set
F4-
03 = 103
to monitor
U1-03 [Output Current]
.
Note:
•
You cannot use all of the monitors in all of the control methods.
•
When you use the terminal in through mode, set this parameter to
000
or
031
. You can use this setting to adjust the V2 terminal output
from PLC through MEMOBUS/Modbus communications or a communications option.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...