5.3 MEMOBUS/Modbus Communications
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
311
•
0002H: Frequency Reference = 60.00 Hz (6000 = 1770H)
•
0004H: Torque Limit = 150.0% (1500 = 05DCH)
When you rewrite the parameter value with the write command through the
H5-11 [Comm ENTER Command
Mode]
setting, you must use the Enter command to save and enable the contents of the changes. Refer to
Comm ENTER Command Mode on page 739
and
for more information.
Table 5.11 Message Example When Writing to Non-Consecutive Holding Registers
Byte
Command Message
Response Message (when normal)
Response Message (when there is a fault)
Setting Data
(Hex.)
Setting Data
(Hex.)
Setting Data
(Hex.)
0
Slave address
01
Slave address
01
Slave address
01
1
Function Code
67
Function Code
67
Function Code
E7
2
Subfunction
Code
Upper
01
Subfunction
Code
Upper
01
Error Codes
02
3
Lower
0E
Lower
0E
CRC-16
Upper
EA
4
Data Qty
Upper
00
Data Qty
Upper
00
Lower
31
5
Lower
02
Lower
02
-
6
Byte No.
Upper
00
CRC-16
Upper
D5
-
7
Lower
04
Lower
FC
-
8
Holding register
1 No.
Upper
00
-
-
9
Lower
02
-
-
10
Holding register
1 data
Upper
17
-
-
11
Lower
70
-
-
12
Holding register
2 No.
Upper
00
-
-
13
Lower
04
-
-
14
Holding register
2 data
Upper
05
-
-
15
Lower
DC
-
-
16
CRC-16
Upper
55
-
-
17
Lower
59
-
-
Note:
The number of bytes set in the command message set the data quantity × 2 during the command message.
◆
Enter Command
When you use MEMOBUS/Modbus communications to write parameters from the PLC to the drive,
H5-11
[Comm ENTER Command Mode]
lets you use the Enter command to enable these parameters. This section gives
information about the Enter command.
■
Types of Enter Commands
The drive supports the two Enter commands shown in
.
Write 0 to register number 0900 or 0910 (Hex.) to enable the Enter command. You can only write to these
registers. If you read to these registers, it will cause an error.
Table 5.12 Types of Enter Commands
Register No.
(Hex.)
Description
0900
When you write parameter data to the EEPROM, you will enable the data on the RAM at the same time.
This process saves the parameter changes even if you de-energize the drive.
0910
This updates the data on the RAM, but does not write data to the EEPROM.
If you de-energize the drive, you will lose the parameter changes.
Note:
•
You can write the EEPROM to the drive a maximum of 100,000 times. Do not frequently execute the Enter command (0900 (Hex.))
that is written to EEPROM.
•
The Enter command register is write-only. If this register is read, it will cause a Register Number Error (02 (Hex.)).
•
When the command data or broadcast message is transmitted to the drive, the Enter command is not necessary.
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...