9.2 Model Specifications (200 V Class)
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
429
9.2
Model Specifications (200 V Class)
Table 9.1 Rating (200 V Class)
Model
2003
2005
2008
2011
2014
2018
2025
2033
2047
2060
2075
Maximum Applicable Motor Output
(kW)
0.55
0.75
1.5
2.2
3
4.0
5.5
7.5
11
15
18.5
Input
Rated
Input
Current
(A)
AC
3.6
4.8
8.9
12.7
17
20.7
30
40.3
58.2
78.4
96
DC
4.5
5.9
11
16
21
25
37
49
71
96
118
Output
Rated Output Capacity
(kVA)
1.2
1.9
3.0
4.2
5.3
6.7
9.5
12.6
17.9
22.9
28.6
Rated Output Current
(A)
3.2
5
8
11
14
17.5
25
33
47
60
75
Overload Tolerance
150% of the rated output current for 60 s
Note:
Derating can be necessary for applications that start and stop frequently.
Carrier Frequency
8 kHz without derating the drive capacity.
Derate the drive capacity to use values to 15 kHz maximum.
Maximum Output
Voltage
Three-phase 200 V to 240 V
Note:
The maximum output voltage is proportional to the input voltage.
Maximum Output
Frequency
•
AOLV (Advanced Open Loop Vector): 120 Hz
•
CL-V/f (Closed Loop V/f Control), CLV (Closed Loop Vector): 400 Hz
•
V/f (V/f Control), OLV (Open Loop Vector): 590 Hz
Measures
for
Harmonics
DC reactor
External options
Braking
Device
Braking Transistor
Standard internal characteristics
EMC
Filter
EMC Filter
IEC61800-3, C3
Factory option
•
Models 2xxxB: There is a category C3 EMC filter in the drive.
Power
Supply
Rated Voltage/Rated
Frequency
•
Three-phase AC power supply 200 V to 240 V at 50/60 Hz
•
DC power supply 270 V to 340 V
Permitted Voltage
Fluctuation
-15% to +10%
Permitted Frequency
Fluctuation
±5%
Input Power
(kVA)
1.5
2.0
3.7
5.3
7.1
8.6
12.5
16.8
24.2
32.6
39.9
*1
The maximum applicable motor output complies with 208 V motor ratings as specified in NEC Table 430.250. The rated output
current of the drive output amps must be equal to or more than the motor rated current.
*2
Assumes the value at the rated output current. The input current rating changes when the power supply transformer, input reactor,
wiring connections, or power supply impedance change.
*3
The rated output capacity is calculated with a rated output voltage of 208 V.
*4
The power supply capacity is calculated with the voltage between lines at 240 V.
Table 9.2 Rating (200 V Class)
Model
2088
2115
2145
2180
2215
2283
2346
2415
Maximum Applicable Motor Output
(kW)
22
30
37
45
55
75
90
110
Input
Rated Input
Current
(A)
AC
82
111
136
164
200
271
324
394
DC
101
136
167
202
245
332
397
483
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...