10.17 Parameters that Change from the Default Settings with A1-02 [Control Method Selection]
552
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
No.
Name
Range
Unit
Control Method (A1-02 Setting)
V/f
(0)
CL-V/f
(1)
OLV
(2)
CLV
(3)
AOLV
(4)
E1-04
Maximum
Output
Frequency
40.0 - 400.0
0.1 Hz
50.0
50.0
50.0
50.0
50.0
E1-05
Maximum
Output Voltage
0.0 - 255.0
0.1 V
200.0
200.0
200.0
200.0
200.0
E1-06
Base Frequency
0.0 - 400.0
0.1 Hz
50.0
50.0
50.0
50.0
50.0
E1-07
Mid Point A
Frequency
0.0 - 400.0
0.1 Hz
2.5
2.5
3.0
-
0.0
E1-08
Mid Point A
Voltage
0.0 - 255.0
0.1 V
15.0
15.0
14.4
-
0.0
E1-09
Minimum Output
Frequency
0.0 - 400.0
0.1 Hz
1.3
1.3
0.5
-
0.0
E1-10
Minimum Output
Voltage
0.0 - 255.0
0.1 V
9.0
9.0
3.0
-
0.0
E1-14
Middle Out Freq
Volt Select 1
0.0 - 255.0
0.1 V
15.0
15.0
14.4
-
0.0
E1-15
Minimum Out
Freq Volt Select
1
0.0 - 255.0
0.1 V
9.0
9.0
3.0
-
0.0
E1-16
Middle Out Freq
Volt Select 2
0.0 - 255.0
0.1 V
15.0
15.0
14.4
-
0.0
E1-17
Minimum Out
Freq Volt Select
2
0.0 - 255.0
0.1 V
9.0
9.0
3.0
-
0.0
E1-18
Middle Out Freq
Volt Select 3
0.0 - 255.0
0.1 V
15.0
15.0
14.4
-
0.0
E1-19
Minimum Out
Freq Volt Select
3
0.0 - 255.0
0.1 V
9.0
9.0
3.0
-
0.0
F1-01
Encoder 1 Pulse
Count (PPR)
0 - 60000
1 ppr
600
600
600
600
600
F1-05
Encoder 1
Rotation
Selection
0 - 1
1
0
0
0
0
0
F1-09
Overspeed
Detection Delay
Time
0.0 - 2.0
0.1 s
-
1.0
-
0.0
0.1
H4-20
Analog Power
Monitor 100%
Level
0.00 - 650.00
0.01
Default value of
E2-11
Default value of
E2-11
Determined by
E2-11
Determined by
E2-11
Determined by
E2-11
L1-01
Motor Overload
(oL1) Protection
0 - 4
1
1
1
1
1
1
L3-05
Stall Prevention
during RUN
0 - 3
1
1
1
-
-
-
L3-20
DC Bus Voltage
Adjustment Gain
0.00 - 5.00
0.01
1.00
1.00
0.30
0.30
0.30
L3-21
OVSuppression
Accel/Decel P
Gain
0.10 - 10.00
0.01
1.00
1.00
1.00
1.00
1.00
L3-36
Current
Suppression
Gain@Accel
0.0 - 100.0
0.1
10.0
10.0
20.0
-
-
L4-01
Speed Agree
Detection Level
0.0 - 400.0
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
L4-02
Speed Agree
Detection Width
0.0 - 20.0
0.1
2.0 Hz
2.0 Hz
2.0 Hz
2.0 Hz
2.0 Hz
L4-03
Speed Agree
Detection Level
(+/-)
-400.0 - +400.0
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
L4-04
Speed Agree
Detection Width
(+/-)
0.0 - 20.0
0.1
2.0 Hz
2.0 Hz
2.0 Hz
2.0 Hz
2.0 Hz
L8-38
Carrier
Frequency
Reduction
0 - 2
1
2
2
2
2
0
L8-40
Carrier Freq
Reduction Off-
Delay
0.00 - 2.00
0.01 s
0.50
0.50
0.50
0.50
0.50
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...