EZZ023535
22 / 35
SA-66 Align Fault Sel
No.
(Hex.)
Name
Description
Default Setting
(Range)
SA-66
(1AD7)
Align Fault Sel
Sets the operation when an Alignment fault is detected. An
Alignment fault is detected when the interval between
Master Trigger and Slave Trigger inputs exceeds the setting
value of SA-67.
Note: 268,435,456 is the maximum encoder pulse count
value between Master Trigger and Slave Trigger inputs. (For
a motor with a 1024 PPR encoder, this is equivalent to
65,536 revolutions.)
0
(0 - 2)
0: Disabled
1: Ignore First Trigger
Disables the position deviation between the first triggers. Use this to prevent the mistaken
detection of the two trigger patterns used for Alignment. For this setting, set SA-67 to a distance
between the sensors of 50% to 70%.
2: Fault
Detects AF (Alignment Fault) and coasts to stop when the position deviation between the
triggers exceeds the setting value of SA-67. When using this mode, it is effective to set the
deviation of SA-67 larger than the normal distance between triggers.
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...