C4-14: M2 Torque Comp Delay Time Sel 1
No.
(Hex.)
Name
Description
Default
(Range)
C4-14
(1116)
RUN
M2 Torque Comp Delay
Time Sel 1
Sets the primary delay time constant for torque compensation for motor 2 when the drive receives
a Reverse run command and
b1-23 = 1 [Selection REV Parameters = Enabled]
.
Determined by E3-01
(0 - 60000 ms)
■
C4-15: Torque Comp Delay Time Select 2
No.
(Hex.)
Name
Description
Default
(Range)
C4-15
(111B)
RUN
Torque Comp Delay Time
Select 2
Sets the primary delay time constant for torque compensation that the drive uses when
b1-23 = 0
[Selection REV Parameters = Disabled]
or
b1-23 = 1 [Enabled]
, and the MFDI
“
Counterweight
Selection
”
setting is ON for the Forward run command.
Determined by A1-02
(0 - 60000 ms)
■
C4-16: Torque Comp Delay Time Select 3
No.
(Hex.)
Name
Description
Default
(Range)
C4-16
(111C)
RUN
Torque Comp Delay Time
Select 3
Sets the primary delay time constant for torque compensation that the drive uses when the reverse
command activates,
b1-23 = 1 [Selection REV Parameters = Enabled]
, and the MFDI
“
Counterweight Selection
”
setting activates.
Determined by A1-02
(0 - 60000 ms)
■
C4-19: Torque Ripple Suppress Min Freq
No.
(Hex.)
Name
Description
Default
(Range)
C4-19
(0B8D)
Expert
Torque Ripple Suppress
Min Freq
If there is slow oscillation at low speeds, adjust this setting. Usually it is not necessary to change
this setting.
0.1 Hz
(0.0 - 10.0 Hz)
Note:
Set
C4-20 [Voltage Compensation Adjust 1] ≠ 0
to enable this parameter.
■
C4-20: Voltage Compensation Adjust 1
No.
(Hex.)
Name
Description
Default
(Range)
C4-20
(0BCB)
Expert
Voltage Compensation
Adjust 1
Sets voltage precision compensation. Usually it is not necessary to change this setting.
120 Hz
(0 - 200 Hz)
Note:
Set
C4-20 = 0
when noise occurs during low-speed operation.
■
C4-21: Voltage Compensation Adjust 2
No.
(Hex.)
Name
Description
Default
(Range)
C4-21
(0BCC)
Expert
Voltage Compensation
Adjust 2
Sets voltage precision compensation. Usually it is not necessary to change this parameter.
Determined by o2-04
(0 - 10)
Note:
Set
C4-21 = 0
when noise occurs during high-speed operation.
■
C4-23: Current Control Gain
No.
(Hex.)
Name
Description
Default
(Range)
C4-23
(1583)
Expert
Current Control Gain
Sets the Current control gain. Usually it is not necessary to change this parameter.
1.00
(0.50 - 2.50)
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...