SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
621
Table 11.15 Wiring Distance
Wiring Distance
Up to 50 m
Up to 100 m
Greater than 100 m
C6-02 [Carrier Frequency Selection]
1 to F (up to 15 kHz)
1 to 2 (up to 5 kHz), 7
1 (up to 2 kHz), 7
■
C6-03: Carrier Frequency Upper Limit
No.
(Hex.)
Name
Description
Default
(Range)
C6-03
(0225)
Carrier Frequency Upper
Limit
Sets the upper limit of the carrier frequency. Set
C6-02 = F [Carrier Frequency Selection = User
Defined (C6-03 to C6-05)]
to set this parameter.
Determined by C6-02
(1.0 - 15.0 kHz)
Setting a Fixed User-Defined Carrier Frequency
When you cannot use
C6-02
to set a carrier frequency between set selectable values, you can set the value in
C6-
03
. The carrier frequency will be fixed to the value set to
C6-03
.
When
A1-02 = 0, 1 [Control Method Selection = V/f, CL-V/f]
, set
C6-03 = C6-04 [Carrier Frequency Lower
Limit]
to fix the carrier frequency.
Setting a Variable Carrier Frequency to Agree with the Output Frequency
When
A1-02 = 0, 1
, set
C6-03
,
C6-04
, and
C6-05 [Carrier Freq Proportional Gain]
as shown in
to
make the carrier frequency change linearly with the output frequency.
Figure 11.40 Setting a Variable Carrier Frequency to Agree with the Output Frequency
Note:
•
When
C6-05 ≤ 7
, the drive disables
C6-04
. The carrier frequency is fixed to the value set to
C6-03
.
•
The drive detects
oPE11 [Carrier Frequency Setting Error]
when these conditions are correct at the same time:
–
C6-05 ≥ 6
–
C6-04 ≥ C6-03
■
C6-04: Carrier Frequency Lower Limit
No.
(Hex.)
Name
Description
Default
(Range)
C6-04
(0226)
Carrier Frequency Lower
Limit
Sets the lower limit of the carrier frequency. Set
C6-02 = F [Carrier Frequency Selection = User
Defined (C6-03 to C6-05)]
to set this parameter.
Determined by C6-02
(1.0 - 15.0 kHz)
Set
C6-03 [Carrier Frequency Upper Limit]
,
C6-04
, and
C6-05 [Carrier Freq Proportional Gain]
to make the
carrier frequency change linearly with the output frequency.
Note:
The drive detects
oPE11 [Carrier Frequency Setting Error]
when these conditions are correct at the same time:
•
C6-04 ≥ C6-03
•
C6-05 ≥ 6
■
C6-05: Carrier Freq Proportional Gain
No.
(Hex.)
Name
Description
Default
(Range)
C6-05
(0227)
Carrier Freq Proportional
Gain
Sets the proportional gain for the carrier frequency. Set
C6-02 = F [Carrier Frequency Selection
= User Defined (C6-03 to C6-05)]
to set this parameter.
Determined by C6-02
(0 - 99)
Set
C6-03 [Carrier Frequency Upper Limit]
,
C6-04 [Carrier Frequency Lower Limit]
, and
C6-05
to make the
carrier frequency change linearly with the output frequency.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...