F4-04: Terminal V2 Gain
No.
(Hex.)
Name
Description
Default
(Range)
F4-04
(0394)
RUN
Terminal V2 Gain
Sets the gain of the monitor signal that is sent from terminal V2. Sets the analog signal output
level from terminal V2 at 10 Vor 20 mA as 100% when an output for monitoring items is 100%.
50.0%
(-999.9 - +999.9%)
The maximum output voltage output from terminal V2 is ±10 V. Use
F4-08 [Terminal V2 Signal Level]
to set the
signal level.
Example settings:
When you use these settings, and the monitored output voltage is at 100% (drive rated current), the output voltage
of terminal V2 is 5 V (50% of 10 V). The output current is 200% of the drive rated current when terminal V2
outputs a maximum voltage of 10 V.
•
F4-03 [Terminal V2 Function Selection] = 103 (U1-03: Output Current)
•
F4-04 = 50.0%
•
F4-06 [Terminal V2 Bias] = 0.0%
•
F4-08 = 0 (0 V to 10 V)
■
F4-05: Terminal V1 Bias
No.
(Hex.)
Name
Description
Default
(Range)
F4-05
(0395)
RUN
Terminal V1 Bias
Sets the bias of the monitor signal that is sent from terminal V1. When an output for monitoring
items is 0%, this parameter sets the analog signal output level from the V1 terminal as a
percentage of 10 Vor 20 mA.
0.0%
(-999.9 - +999.9%)
The maximum output voltage output from terminal V1 is ±10 V. Use
F4-07 [Terminal V1 Signal Level]
to set the
signal level.
■
F4-06: Terminal V2 Bias
No.
(Hex.)
Name
Description
Default
(Range)
F4-06
(0396)
RUN
Terminal V2 Bias
Sets the bias of the monitor signal that is sent from terminal V2. Set the level of the analog signal
sent from the V2 terminal at 10 Vor 20 mA as 100% when an output for monitoring items is 0%.
0.0%
(-999.9 - +999.9%)
The maximum output voltage output from terminal V2 is ±10 V. Use
F4-08 [Terminal V2 Signal Level]
to set the
signal level.
■
F4-07: Terminal V1 Signal Level
No.
(Hex.)
Name
Description
Default
(Range)
F4-07
(0397)
Terminal V1 Signal Level
Sets the output signal level for terminal V1.
0
(0, 1)
0 : 0 to 10 V
1 : -10 to 10 V
■
F4-08: Terminal V2 Signal Level
No.
(Hex.)
Name
Description
Default
(Range)
F4-08
(0398)
Terminal V2 Signal Level
Sets the output signal level for terminal V2.
0
(0, 1)
0 : 0 to 10 V
1 : -10 to 10 V
◆
F5: Digital Output Option
F5 parameters
set the output mode and function of output signals when you use digital output option card DO-A3.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...