Code
Name
Causes
Possible Solutions
oPE08
Parameter Selection Error
A function was set that is not compatible with the
control method selected in
A1-02 [Control Method
Selection]
.
1. Push
to show
U1-18 [oPE Fault Parameter]
, and find
parameters that are not in the applicable setting range.
2. Set the parameters correctly.
Note:
If more than one error occurs at the same time, other
oPExx
errors have priority over
oPE02
.
These parameters were set in OLV Control:
•
n2-02 > n2-03 [Automatic Freq Regulator Time
1 > Automatic Freq Regulator Time 2]
•
C4-02 > C4-06 [Torque Compensation Delay
Time > Motor 2 Torque Comp Delay Time]
•
Set
n2-02 < n2-03
.
•
Set
C4-02 < C4-06
.
Code
Name
Causes
Possible Solutions
oPE10
V/f Data Setting Error
The parameters that set the V/f pattern do not
satisfy the following conditions:
•
For motor 1:
E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤
E1-04 [Minimum Output Frequency ≤ Mid Point
A Frequency < Base Frequency ≤ Mid Point B
Frequency ≤ Maximum Output Frequency]
•
For motor 2:
E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤
E3-04 [Minimum Output Frequency ≤ Mid Point
A Frequency < Base Frequency ≤ Mid Point B
Frequency ≤ Maximum Output Frequency]
•
For motor 3:
E7-09 ≤ E7-07 < E7-06 ≤ E7-11 ≤
E7-04 [Minimum Output Frequency ≤ Mid Point
A Frequency < Base Frequency ≤ Mid Point B
Frequency ≤ Maximum Output Frequency]
Set the parameters correctly to satisfy the conditions.
Code
Name
Causes
Possible Solutions
oPE11
Carrier Frequency Setting Error
These parameters are set at the same time:
•
C6-05 > 6 [Carrier Freq Proportional Gain >
6]
•
C6-04 > C6-03 [Carrier Frequency Lower Limit
> Carrier Frequency Upper Limit]
Note:
When
C6-05 < 7
,
C6-04
becomes disabled. The
drive sets the carrier frequency to the value set
to
C6-03
.
C6-02 to C6-05
settings are not in the applicable
setting range.
Set
C6-02 to C6-05
correctly.
Code
Name
Causes
Possible Solutions
oPE18
Online Tuning Param Setting Err
The parameters that control online tuning are set
incorrectly. In OLV control, one of these parameters
was set when
n6-01 = 2 [Online Tuning Selection =
Voltage Correction Tuning]
:
•
E2-02 [Motor Rated Slip]
is set to 30% of the
default setting or lower.
•
E2-06 [Motor Leakage Inductance]
is set to 50%
of the default setting or lower.
•
E2-03 = 0 [Motor No-Load Current = 0 A]
has
been set.
Set
E2-02, E2-03, and E2-06
correctly.
Code
Name
Causes
Possible Solutions
oPE22
Parameter Setting Error
The crane sequence parameter (frequency) setting
error for motor 1.
Set the parameters correctly.
When
S1-04 ≠ 0 [Brake Delay Time ≠ 0.00 s]
, set in
these ways.
•
S1-01 or S1-02 > S1-03 [Brake Release
Frequency > Brake Delay Frequency]
•
S1-03
>
E1-06 [Brake Delay Frequency > Base
Frequency]
•
S1-03
>
S4-06 [Brake Delay Frequency >
Light-load 1 Detect Frequency]
Set the parameters correctly so that these conditions are satisfied.
•
S1-02 and S1-02
≦
S1-03
•
S1-03
≦
E1-06
•
S1-03
≦
S4-06
When
S1-04 = 0
, set in these ways.
•
S1-01 or S1-02 > E1-06 [Brake Release
Frequency > Base Frequency]
•
S1-01 or S1-02 > S4-06 [Brake Release
Frequency > Light-load 1 Detect Frequency]
Set the parameters correctly so that these conditions are satisfied.
•
S1-01 and S1-02
≦
E1-06
•
S1-01 and S1-02
≦
S4-06
When
S1-15 ≠ 0 [Slip Prevention Time ≠ 0.00 s]
, set
in these ways.
•
S1-12 or S1-13 < S1-14 [Brake Hold Frequency
< Slip Prevention Frequency]
•
S1-12 or S1-13 = E1-09 = S1-14 [Brake Hold
Frequency = Minimum Output Frequency = Slip
Prevention Frequency]
Set the parameters correctly so that these conditions are satisfied.
•
S1-12 or S1-13
≧
S1-14 [Brake Hold Frequency
≧
Slip
Prevention Frequency]
•
S1-12 and S1-13 ≠ E1-09 ≠ S1-14 [Brake Hold Frequency ≠
Minimum Output Frequency ≠ Slip Prevention Frequency]
When
H1-xx = 35 [MFDI Function Select = Impact
Stop Enable]
, set
S3-01
≦
S1-12 or S1-13 [Impact
Stop Creep Frequency
≦
Brake Hold Frequency]
.
Make sure that
S3-01 > S1-12 and S1-13
.
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...