269
3.
Ground the wire shielding in the drive side and motor side.
A - Drive Series
B - 10 m (32.8 ft.) maximum
C - Motor
D - Metal conduit
E - Grounding wire
Figure 4.15 Wiring the Drive and Motor
Note:
•Use a braided shield cable for the drive and motor wiring or put the wires through a metal conduit.
•The maximum wiring length between the drive and motor is 10 m (32.8 ft.). Keep the cable between the drive and motor as
short as possible.
•Keep the grounding wire as short as possible.
4.
Use a cable clamp to ground the motor cable to the metal plate.
Note:
Make sure that the protective ground wire complies with technical specifications and local safety standards.
A - Braided shield cable
B - Metal plate
C - Cable clamp (conductive)
Figure 4.16 Ground the shield