5.3 MEMOBUS/Modbus Communications
320
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
Register No.
(Hex.)
Description
004B
U1-12 [Drive Status]
bit 0
1: During run
bit 1
1: During zero speed
bit 2
1: During reverse
bit 3
1: During reset signal input
bit 4
1: During speed agreement
bit 5
1: Drive operation ready
bit 6
1: Minor Fault
bit 7
1: Fault
bit 8
1: oPExx [Operation Error] generation
bit 9
1: Momentary power loss ride-thru
bit A
1: Motor 2 Selection
bit B
Reserved
bit C
1: Motor 3 Selection
bit D
Reserved
bit E
ComRef status/ NetRef status
bit F
ComCtrl status/ NetCtrl status
004C - 007E
Use with
U1-xx, U4-xx, U6-xx [Monitors]
. Refer to
“
U2: Fault Trace
”
and
“
U3: Fault History
”
for details.
007F
Minor fault code (Refer to
“
Minor Fault Description
”
for more information about the minor fault codes.)
0080 - 0097
Use with
U2-xx, U3-xx [Monitors]
. Refer to
“
U Monitor
”
for details, and refer to
“
Fault Trace/Fault History Descriptions
”
for details about register values.
0098 - 0099
U4-01 [Cumulative Ope Time]
Example: When
U4-01 [Cumulative Ope Time]
is 12345, 0098 (Hex.) = 1234 and 0099 (Hex.) = 5.
009A - 009B
U4-03 [Cooling Fan Ope Time]
Example: When
U4-03 [Cooling Fan Ope Time]
is 12345, 009A (Hex.) = 1234 and 009B (Hex.) = 5.
009C - 00AA
Reserved
00AB
Drive rated current
Note:
The unit of display varies depending on the model.
2003 to 2033, 4002 to 4018: 0.01 A
2047 to 2415, 4024 to 4605: 0.1 A
00AC
U1-05 [Motor Speed]
Units: min
-1
or r/min
Note:
Set
E2-04, E4-04 [Motor Poles]
.
00AD
Units: 0.01%
00AE, 00AF
Reserved
00B0
Optional codes connected to
CN5-A
Optional connected codes are stored in the register.
AI-A3 = 0003 (Hex.)
AO-A3 = 0004 (Hex.)
DI-A3 = 0001 (Hex.)
DO-A3 = 0002 (Hex.)
PG-B3 = 0011 (Hex.)
PG-RT3 = 0023 (Hex.)
PG-X3 = 0012 (Hex.)
SI-C3 = 5343 (Hex.)
SI-EM3 = 1005 (Hex.)
SI-EN3 = 1006 (Hex.)
SI-EP3 = 1007 (Hex.)
SI-ET3 = 1004 (Hex.)
SI-N3 = 534E (Hex.)
SI-P3 = 5350 (Hex.)
SI-S3 = 5353 (Hex.)
SI-T3 = 5354 (Hex.)
00B1
Reserved
00B2
Optional codes connected to CN5-B
00B3
Optional codes connected to CN5-C
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...