736
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
Calibrate Terminal AM
The output signal is adjustable while the drive is stopped. Use the following procedure to perform calibration.
1. Show
H4-05 [Terminal AM Analog Output Gain]
on the keypad.
The analog signal at the time when the monitor item selected with
H4-04 [Terminal AM Analog Output
Select]
is 100% is output from terminal AM.
2. Adjust
H4-05
while referencing the meter scale connected to terminal AM.
3. Show
H4-06 [Terminal AM Analog Output Bias]
on the keypad.
The analog signal at the time when the monitor item selected with
H4-04
is 0% is output from terminal AM.
4. Adjust
H4-06
while referencing the meter scale connected to terminal AM.
■
H4-01: Terminal FM Analog Output Select
No.
(Hex.)
Name
Description
Default
(Range)
H4-01
(041D)
Terminal FM Analog
Output Select
Sets the monitor number to send from MFAO terminal FM.
102
(000 - 999)
Set the
x-xx
part of the
Ux-xx [Monitor]
. For example, set
H4-01 = 102
to monitor
U1-02 [Output Frequency]
.
Note:
•
You cannot use all of the monitors in all of the control methods.
•
When you use the terminal in through mode, set this parameter to
000
or
031
. You can set the terminal FM output level from the PLC
through MEMOBUS/Modbus communications or the communication option.
■
H4-02: Terminal FM Analog Output Gain
No.
(Hex.)
Name
Description
Default
(Range)
H4-02
(041E)
RUN
Terminal FM Analog
Output Gain
Sets the gain of the
Ux-xx
monitor signal set in
H4-01 [terminals FM Monitor Selection]
.
100.0%
(-999.9 - +999.9%)
The analog signal output from the terminal FM is a maximum of ±10 V. Select the signal level with
H4-07
[Terminal FM Signal Level Select]
.
■
H4-03: Terminal FM Analog Output Bias
No.
(Hex.)
Name
Description
Default
(Range)
H4-03
(041F)
RUN
Terminal FM Analog
Output Bias
Sets the bias of the
Ux-xx
monitor signal set in
H4-01 [Terminal FM Analog Output Select]
.
0.0%
(-999.9 - +999.9%)
The analog signal output from the terminal FM is a maximum of ±10 V. Select the signal level with
H4-07
[Terminal FM Signal Level Select]
.
■
H4-04: Terminal AM Analog Output Select
No.
(Hex.)
Name
Description
Default
(Range)
H4-04
(0420)
Terminal AM Analog
Output Select
Sets the monitoring number to be output from the MFAO terminal AM.
103
(000 - 999)
Set the
x-xx
part of the
Ux-xx [Monitor]
. For example, set
H4-04 = 103
to monitor
U1-03 [Output Current]
.
Note:
•
You cannot use all of the monitors in all of the control methods.
•
When you use the terminal in through mode, set this parameter to
000
or
031.
You can set the terminal AM output level from the PLC
through MEMOBUS/Modbus communications or the communication option.
■
H4-05: Terminal AM Analog Output Gain
No.
(Hex.)
Name
Description
Default
(Range)
H4-05
(0421)
RUN
Terminal AM Analog
Output Gain
Sets the gain of the
Ux-xx
monitor signal set in
H4-04 [terminals AM Monitor Selection]
.
50.0%
(-999.9 - +999.9%)
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...