646
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
■
E3-13: Motor 2 Base Voltage
No.
(Hex.)
Name
Description
Default
(Range)
E3-13
(0347)
Expert
Motor 2 Base Voltage
Sets the base voltage for the motor 2 V/f pattern. Set this parameter to adjust the V/f pattern for
the constant output range. Usually it is not necessary to change this parameter.
0.0 V
(200 V Class: 0.0 to 255.0
V, 400 V Class: 0.0 to 510.0
V)
Note:
•
When you initialize the drive, this parameter is reset to the default value.
•
The setting value changes automatically when you do Auto-Tuning (rotational and stationary 1 or 2).
■
E3-14: M2 Middle Out Freq Volt Select
No.
(Hex.)
Name
Description
Default
(Range)
E3-14
(114E)
M2 Middle Out Freq Volt
Select
Sets the mid point A voltage for motor 2 reverse run used when
b1-23 = 1 [Selection REV
Parameters = Enabled]
.
Determined by E3-01 and
E1-03
(200 V Class: 0.0 to 255.0
V, 400 V Class: 0.0 to 510.0
V)
■
E3-15: M2 Minimum Out Freq Volt Select
No.
(Hex.)
Name
Description
Default
(Range)
E3-15
(114F)
M2 Minimum Out Freq
Volt Select
Sets the minimum output voltage for motor 2 reverse run used when
b1-23 = 1 [Selection REV
Parameters = Enabled]
.
Determined by E3-01 and
E1-03
(200 V Class: 0.0 to 255.0
V, 400 V Class: 0.0 to 510.0
V)
■
E3-20: UL Motor2 Sel
No.
(Hex.)
Name
Description
Default
(Range)
E3-20
(0BF4)
UL Motor2 Sel
Sets the motor characteristics.
2
(0 - 2)
0 : Constant Torque
1 : Variable Torque
2 : Auto Distinction
◆
E4: Motor 2 Parameters
E4 parameters [Motor 2 Parameters]
set induction motor data. To switch drive operation from one motor to a
different motor, configure motor 2.
Auto-Tuning automatically sets the
E4 parameters
to the best values for the application. If you cannot do Auto-
Tuning, set the
E4 parameters
manually.
Note:
E3-xx
and
E4-xx
are available when
H1-xx = 16 [MFDI Function Select = Motor 2 Selection]
.
■
E4-01: Motor 2 Rated Current
No.
(Hex.)
Name
Description
Default
(Range)
E4-01
(0321)
Motor 2 Rated Current
Sets the motor rated current for motor 2 in amps.
Determined by o2-04
(10% to 200% of the drive
rated current)
Note:
•
If
E4-01 ≤ E4-03 [Motor 2 Rated No-Load Current]
is set,
oPE02 [Parameter Range Setting Error]
will be detected.
•
The default settings and setting ranges appear in the following units:
–
2003 to 2033, 4002 to 4018: 0.01 A units
–
2047 to 2415, 4024 to 4605: 0.1 A units
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...