662
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
■
F3-20: Terminal DA Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
F3-20
(0BED)
Expert
Terminal DA Function
Selection
Sets the function for terminal DA of the DI-A3 when
F3-01 = 8 [Digital Input Function Selection
= Multi-Function Digital Input]
.
F
(0 - 1FF)
■
F3-21: Terminal DB Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
F3-21
(0BEE)
Expert
Terminal DB Function
Selection
Sets the function for terminal DB of the DI-A3 when
F3-01 = 8 [Digital Input Function Selection
= Multi-Function Digital Input]
.
F
(0 - 1FF)
■
F3-22: Terminal DC Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
F3-22
(0BEF)
Expert
Terminal DC Function
Selection
Sets the function for terminal DC of the DI-A3 when
F3-01 = 8 [Digital Input Function Selection
= Multi-Function Digital Input]
.
F
(0 - 1FF)
■
F3-23: Terminal DD Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
F3-23
(0BF0)
Expert
Terminal DD Function
Selection
Sets the function for terminal DD of the DI-A3 when
F3-01 = 8 [Digital Input Function Selection
= Multi-Function Digital Input]
.
F
(0 - 1FF)
■
F3-24: Terminal DE Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
F3-24
(0BF1)
Expert
Terminal DE Function
Selection
Sets the function for terminal DE of the DI-A3 when
F3-01 = 8 [Digital Input Function Selection
= Multi-Function Digital Input]
.
F
(0 - 1FF)
■
F3-25: Terminal DF Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
F3-25
(0BF2)
Expert
Terminal DF Function
Selection
Sets the function for terminal DF of the DI-A3 when
F3-01 = 8 [Digital Input Function Selection
= Multi-Function Digital Input]
.
F
(0 - 1FF)
◆
F4: Analog Monitor Option
F4 parameters
set drive operation when you use analog monitor option card AO-A3. The AO-A3 card has 2
output terminals (terminals V1 and V2) for signals with an Output resolution of 11 bits (1/2048) + encoding and
that have an output voltage range of -10 V to +10 V. Install the AO-A3 card to a drive to output analog signals
that monitor the output status of the drive (output frequency and output current).
Refer to the AO-A3 card manual for more information about how to install, wire, and set the AO-A3 card.
Use the
U monitor
number to set the monitor data to be output from terminals V1 and V2 on the AO-A3 card.
Enter the last three digits of
Ux-xx
as the setting value.
•
Use Gain and Bias to Adjust the Output Signal Level of Terminal V1
You must stop the drive to adjust the output signal. Use this procedure to calibrate the drive:
1. View the
F4-02 [Terminal V1 Gain]
value on the keypad.
Terminal V1 will output a voltage = 100% of the monitor set in
F4-01 [Terminal V1 Function Selection]
.
2. View the monitor connected to terminal V1 and adjust
F4-02
.
3. View the
F4-05 [Terminal V1 Bias]
value on the keypad.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...