YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
593
■
b1-21 CLV Start Selection
No.
(Hex.)
Name
Description
Default
(Range)
b1-21
(0748)
Expert
CLV Start Selection
Sets the conditions for the drive to accept the Run command when the motor speed is at least the
setting value of
b2-01
or less than the setting value of
E1-09
. Usually it is not necessary to change
this setting.
0
(0, 1)
0 : Reject RUN if b2-01<U1-05<E1-09
The Run command input is not accepted when the motor speed is at least the setting value of
b2-01
or less than
the setting value of
E1-09
.
1 : Accept RUN Command at Any Speed
The Run command input is accepted when the motor speed is at least the setting value of
b2-01
or less than the
setting value of
E1-09
.
■
b1-23: Selection REV Parameters
No.
(Hex.)
Name
Description
Default
(Range)
b1-23
(0B1D)
Selection REV Parameters
Sets the operation of reverse parameters.
0
(0, 1)
0 : Disabled
The drive operates with forward operation parameters.
1 : Enabled
The drive operates with reverse operation parameters during reverse operation.
■
b1-35: Digital Input Deadband Time
No.
(Hex.)
Name
Description
Default
(Range)
b1-35
(1117)
Expert
Digital Input Deadband
Time
Sets the deadband time for MFDIs.
0.0 ms
(0.0 to 100.0 ms)
When the on/off time for MFDIs is longer than the time set in
b1-35
, the drive activates the MFDI. Set this
parameter to prevent malfunctions caused by relay chattering for applications in which relays send input to MFDI
terminals.
◆
b2: DC Injection Braking
b2 parameters
set DC Injection Braking.
DC Injection Braking: A braking method that injects DC current into the motor windings. This function should
not be used too frequently, because it generates a fair amount of heat in the motor.
■
b2-01: DC Injection/Zero SpeedThreshold
No.
(Hex.)
Name
Description
Default
(Range)
b2-01
(0189)
DC Injection/Zero
SpeedThreshold
Sets the frequency to start DC Circuit Braking and Zero Servo.
0.5
(0.0 - 10.0 Hz)
Note:
This parameter is available when
b1-03 = 0 [Stopping Method Selection = Ramp to Stop]
.
When the control method selected in
A1-02 [Control Method Selection]
changes, the
b2-01
function changes.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...