11.11 o: Keypad-Related Settings
798
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
■
o5-03: Log Monitor Data 1
No.
(Hex.)
Name
Description
Default
(Range)
o5-03
(1553)
RUN
Log Monitor Data 1
Sets the data log monitor. This parameter is only available when using an LCD keypad.
101
(000, 101 - 999)
Note:
Set the number of the
U monitor
to record the data log.
For example, to show
U1-01 [Frequency Reference]
, set
o5-03 = 101
. When it is not necessary to set data log monitors, set this
parameter to
000
. You cannot set
U2 monitor [Fault Trace]
or
U3 Monitor [Fault History]
.
■
o5-04: Log Monitor Data 2
No.
(Hex.)
Name
Description
Default
(Range)
o5-04
(1554)
RUN
Log Monitor Data 2
Sets the data log monitor. This parameter is only available when using an LCD keypad.
102
(000, 101 - 999)
Note:
Set the
U monitor
number you will log.
For example, to show
U1-02 [Output Frequency]
, set
o5-04 = 102
. When it is not necessary to set data log monitor, set this parameter to
000
.
■
o5-05: Log Monitor Data 3
No.
(Hex.)
Name
Description
Default
(Range)
o5-05
(1555)
RUN
Log Monitor Data 3
Sets the data log monitor. This parameter is only available when using an LCD keypad.
103
(000, 101 - 999)
Note:
Sets the number of the
U monitor
you will log.
For example, to show
U1-03 [Output Current]
, set
o5-05 = 103
. When it is not necessary to set data log monitors, set this parameter to
000
. You cannot select
U2 monitor [Fault Trace]
or
U3 Monitor [Fault History]
.
■
o5-06: Log Monitor Data 4
No.
(Hex.)
Name
Description
Default
(Range)
o5-06
(1556)
RUN
Log Monitor Data 4
Sets the data log monitor. This parameter is only available when using an LCD keypad.
107
(000, 101 - 999)
Note:
Sets the number of the
U monitor
you will log.
For example, to show
U1-07 [DC Bus Voltage]
, set
o5-06 = 107
. When it is not necessary to set data log monitors, set this parameter to
000
. You cannot select
U2 monitor [Fault Trace]
or
U3 Monitor [Fault History]
.
■
o5-07: Log Monitor Data 5
No.
(Hex.)
Name
Description
Default
(Range)
o5-07
(1557)
RUN
Log Monitor Data 5
Sets the data log monitor. This parameter is only available when using an LCD keypad.
108
(000, 101 - 999)
Note:
Sets the number of the
U monitor
you will log.
For example, to show
U1-08 [Output Power]
, set
o5-07 = 108
. When it is not necessary to set data log monitors, set this parameter to
000
. You cannot select
U2 monitor [Fault Trace]
or
U3 Monitor [Fault History]
.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...