Setting Value
Function
Description
Ref.
2
Speed Agree 1
The terminal deactivates when the output frequency is in the range of the frequency reference ±
L4-02 [Speed
Agree Detection Width]
.
Note:
•
The detection function operates in the two motor rotation directions.
•
The drive outputs the motor speed status when
A1-02 = 3 [Control Method Selection = CLV]
. The drive
outputs the motor speed status when
A1-02 = 4 [Control Method Selection = AOLV]
and
n4-72 = 1 [Speed
Feedback Mode = With Encoder]
.
ON : The output frequency is in the range of
“
frequency reference ±
L4-02
”
.
OFF : The output frequency does not align with the frequency reference although the drive is running.
3
User-Set Speed Agree 1
The terminal activates when the output frequency is in the range of
L4-01 [Speed Agree Detection Level]
±
L4-02
[Speed Agree Detection Width]
and in the range of the frequency reference ±
L4-02
.
Note:
•
The detection function operates in the two motor rotation directions. The drive uses the
L4-01
value as the
forward/reverse detection level.
•
The drive outputs the motor speed status when
A1-02 = 3 [Control Method Selection = CLV]
. The drive
outputs the motor speed status when
A1-02 = 4 [Control Method Selection = AOLV]
and
n4-72 = 1 [Speed
Feedback Mode = With Encoder]
.
ON : The output frequency is in the range of
“
L4-01
±
L4-02
”
and the range of frequency reference ±
L4-02
.
OFF : The output frequency is not in the range of
“
L4-01
±
L4-02
”
nor the range of frequency reference ±
L4-02
.
4
Frequency Detection 1
The terminal deactivates when the output frequency >
“
L4-01 [Speed Agree Detection Level]
+
L4-02 [Speed
Agree Detection Width]
”
. After the terminal deactivates, the terminal stays deactivated until the output frequency is
at the value of
L4-01
.
Note:
•
The detection function operates in the two motor rotation directions. The drive uses the
L4-01
value as the
forward/reverse detection level.
•
The drive outputs the motor speed status when
A1-02 = 3 [Control Method Selection = CLV]
. The drive
outputs the motor speed status when
A1-02 = 4 [Control Method Selection = AOLV]
and
n4-72 = 1 [Speed
Feedback Mode = With Encoder]
.
ON : The output frequency <
L4-01
, or the output frequency ≤
“
L4-01
+
L4-02
”
OFF : The output frequency >
“
L4-01
+
L4-02
”
5
Frequency Detection 2
The terminal activates when the output frequency >
L4-01 [Speed Agree Detection Level]
. After the terminal
activates, the terminal stays activated until the output frequency is at the value of
“
L4-01
-
L4-02
”
.
Note:
•
The detection function operates in the two motor rotation directions. The drive uses the
L4-01
value as the
forward/reverse detection level.
•
The drive outputs the motor speed status when
A1-02 = 3 [Control Method Selection = CLV]
. It also outputs
the motor speed status when
A1-02 = 4
and
n4-72 = 1 [Speed Feedback Mode = With Encoder]
.
ON : The output frequency >
L4-01
OFF : The output frequency <
“
L4-01
-
L4-02
”
, or the output frequency ≤
L4-01
6
Drive Ready
The terminal activates when the drive is ready and running.
7
DC Bus Undervoltage
The terminal activates when the DC bus voltage or control circuit power supply is at the voltage set in
L2-05
[Undervoltage Detection Lvl (Uv1)]
or less. The terminal also activates when there is a fault with the DC bus
voltage.
ON : The DC bus voltage ≤
L2-05
OFF : The DC bus voltage >
L2-05
8
During Baseblock (N.O.)
The terminal activates during baseblock. When the drive is in baseblock, the drive output transistor stops switching
and does not make DC bus voltage.
ON : During baseblock
OFF : The drive is not in baseblock.
9
Frequency Reference
from Keypad
Shows the selected frequency reference source.
ON : The keypad is the frequency reference source.
OFF : Parameter
b1-01 or b1-15 [Frequency Reference Selection 1 or 2]
is the frequency reference source.
A
Run Command Source
Shows the selected Run command source.
ON : The keypad is the Run command source.
OFF : Parameter
b1-02 or b1-16 [Run Command Selection 1 or 2]
is the Run command source.
B
Torque Detection 1 (N.
O.)
The terminal activates when the drive detects overtorque.
ON : The output current/torque >
L6-02 [Torque Detection Level 1]
for longer than the time set in
L6-03 [Torque
Detection Time 1]
.
C
Frequency Reference
Loss
The terminal activates when the drive detects a loss of frequency reference.
D
Braking Resistor Fault
The terminal activates when the mounting-type braking resistor is overheating or when there is a braking transistor
fault.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...