SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
ON : The output frequency is less than the value of
L4-01
or is not more than the value of
L4-01
+
L4-02
.
OFF : The output frequency >
L4-01
+
L4-02
.
Figure 11.63 Frequency Detection 1 Time Chart
Note:
shows the result of the configuration when
L4-07 = 1 [Speed Agree Detection Selection = Detection Always Enabled]
. The
default setting of
L4-07
is
0 [No detection during baseblock]
. When the speed agreement detection selection is
“
No Detection during
Baseblock
”
, the terminal is deactivated when the drive output stops.
■
5: Frequency Detection 2
Setting Value
Function
Description
5
Frequency Detection 2
The terminal activates when the output frequency >
L4-01 [Speed Agree Detection Level]
. After the terminal activates, the
terminal stays activated until the output frequency is at the value of
“
L4-01
-
L4-02
”
.
Note:
•
The detection function operates in the two motor rotation directions. The drive uses the
L4-01
value as the forward/reverse detection
level.
•
The drive outputs the motor speed status when
A1-02 = 3 [Control Method Selection = CLV]
. It also outputs the motor speed status
when
A1-02 = 4
and
n4-72 = 1 [Speed Feedback Mode = With Encoder]
.
ON : The output frequency is more than
L4-01
.
OFF : The output frequency is less than “
L4-01
-
L4-02
,” or it is not more than
L4-01
.
Figure 11.64 Frequency Detection 2 Time Chart
■
6: Drive Ready
Setting Value
Function
Description
6
Drive Ready
The terminal activates when the drive is ready and running.
The terminal deactivates in these conditions:
•
When the power supply is OFF
•
During a fault
•
When there is problem with the control power supply
•
When there is a parameter setting error and the drive cannot operate although there is a Run command
•
When you enter a Run command and it immediately triggers an overvoltage or undervoltage fault because the
drive has an overvoltage or undervoltage fault during stop
•
When the drive is in Programming Mode and will not accept a Run command
•
When the Safe Disable function is active
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...