YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
641
■
E1-17: Minimum Out Freq Volt Select 2
No.
(Hex.)
Name
Description
Default
(Range)
E1-17
(034F)
Minimum Out Freq Volt
Select 2
Sets the minimum output voltage used when
H1-xx = 38 [MFDI Function Selection =
Counterweight Selection]
is ON.
Determined by A1-02 and
E1-03
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
■
E1-18: Middle Out Freq Volt Select 3
No.
(Hex.)
Name
Description
Default
(Range)
E1-18
(0354)
Middle Out Freq Volt Select
3
Sets the mid point A voltage for reverse run used when
b1-23 = 1 [Selection REV Parameters =
Enabled]
and
H1-xx = 38 [MFDI Function Selection = Counterweight Selection]
is ON.
Determined by A1-02 and
E1-03
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
■
E1-19: Minimum Out Freq Volt Select 3
No.
(Hex.)
Name
Description
Default
(Range)
E1-19
(0355)
Minimum Out Freq Volt
Select 3
Sets the minimum output voltage for reverse run used when
b1-23 = 1 [Selection REV
Parameters = Enabled]
.
Determined by A1-02 and
E1-03
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
■
E1-20: UL Motor1 Sel
No.
(Hex.)
Name
Description
Default
(Range)
E1-20
(0BF3)
UL Motor1 Sel
Sets the motor characteristics.
2
(0 - 2)
0 : Constant Torque
1 : Variable Torque
2 : Auto Distinction
◆
E2: Motor Parameters
E2 parameters [Motor Parameters]
are used to set induction motor data. To switch drive operation from one
motor to another motor, set the first motor (motor 1).
Performing Auto-Tuning automatically sets the
E2 parameters
to the optimal values. If Auto-Tuning cannot be
performed, set the
E2 parameters
manually.
■
E2-01: Motor Rated Current (FLA)
No.
(Hex.)
Name
Description
Default
(Range)
E2-01
(030E)
Motor Rated Current (FLA)
Sets the motor rated current in amps.
Determined by o2-04
(10% to 200% of the drive
rated current)
Note:
•
If parameter
E2-01 < E2-03 [Motor No-Load Current]
is set,
oPE02 [Parameter Range Setting Error]
will be detected.
•
The units for the default setting and setting range vary depending on the model of the drive.
–
2003 to 2033, 4002 to 4018: 0.01 A units
–
2047 to 2415, 4024 to 4605: 0.1 A units
The value set for
E2-01
becomes the reference value for motor protection and the torque limit. Enter the motor
rated current as shown on the motor nameplate. The value of
E2-01
is automatically set to the value input for
“
Motor Rated Current
”
by the Auto-Tuning process.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...