INSTRUCTION MANUAL

SAVE THIS INSTRUCTIONS

Si-36 Inverter

THIS PRODUCT CONTAINS A RECHARGEABLE LI-ION BATTERY.
THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY.

Li-ion

UNIVERSAL MINI INVERTER
PURE SINUSOIDAL AC OUTPUT
OUTPUT VOLTAGE AUTO SETTING EQUAL TO INPUT VOLTAGE
POWER SHARE TECHNOLOGY FOR HIGH WATTAGE CONNECTED LOADS 

IMPORTANT SAFEGUARDS

WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE FOLLOWED, INCLUDING THE FOLLOWING

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

  1.  To prevent electric shock, switch off the mains power supply until installation is complete and AC 
       input power is supplied to this product.

  2.  This product requires an unswitched AC power supply of 120-277V, 50/60Hz.

  3.  Make sure all connections are in accordance with the National Electrical code and any local 
       regulations.

  4.  To reduce the risk of electrical shock, disconnect both normal power, emergency power supplies 
       and unit connector of this product before servicing.
 
  5.  For emergency operation of LED, incandescent, fluorescent fixtures and screw-base lamps.

  6.  Use this product in 0°C minimum, 55°C maximum ambient temperatures (Ta). To ensure the 
       emergency operating time over 90 minutes, the output emergency power of Si-36 should be 

Max. 36W with auto adjust for 0-10V dimming installations and operating temperatures between 

       10°C≤ Ta ≤55°C. The Max. load for non dimmed loads must be limited to 36W at operating 
       temperatures range of 10°C≤ Ta ≤ 55°C and 27W between 0°C≤ Ta ≤ 55°C. Contact Factory for 
       details regarding 2 hour run time applications.

  7.  This product is suitable for use in dry or damp locations. Do not use outdoors. Do not mount 
       it near gas, heaters, air outlets or other hazardous locations.

  8.  Do not attempt to service the batteries. A sealed, non-maintenance battery is used that is not 
       field replaceable. Contact the manufacturer for information or service. 

  9.  The use of accessory equipment not recommended by the manufacturer may cause an unsafe 
       condition and void warranty.
 
10.  Do not use this product for other than intended use.

11.  Installation and service should be performed by qualified service personnel.

12.  This product should be mounted in locations and at heights where it will not readily be subjected 
       to tampering by unauthorized personnel.

   

Assurance Emergency Lighting, a division of Assurance Engineering LLC, 357 Cumberland Street  Memphis, TN 38112 1-877-774-4775  AssuranceLighting.com

E506473

Assurance

Emergency Lighting

a d i v i s i o n o f A s s u r a n c e E n g i n e e r i n g L L C

10.2020

Summary of Contents for Emergency Lighting Si-36

Page 1: ...perating time over 90 minutes the output emergency power of Si 36 should be Max 36W with auto adjust for 0 10V dimming installations and operating temperatures between 10 C Ta 55 C The Max load for non dimmed loads must be limited to 36W at operating temperatures range of 10 C Ta 55 C and 27W between 0 C Ta 55 C Contact Factory for details regarding 2 hour run time applications 7 This product is s...

Page 2: ...G SPECIFICATIONS 2 INSTALLING THE Si 36 The Si 36 can be mounted inside or outside nearby or on top of the luminaire 3 INSTALLING THE LED TEST SWITCH LTS Select a convenient location for the LED test switch so that it can be seen after installation Drill a 1 2 12 mm hole for mounting the LED test switch Connect the wires from the LED test switch to the Si 36 according to the wiring diagram on page...

Page 3: ...er to the wiring diagrams below Make connections in the following order 1 2 3 4 5 6 7 3 Consult the factory for other wiring diagrams www AssuranceLighting com ANY QUANTITY 0 10 VDC NORMAL 3 VDC STANDARD 2 VDC ALTERNATE EMERGENCY OPERATION Si 36 YELLOW BLACK GREEN YELLOW WHITE NEUTRAL GROUND HOT LED Test Switch 120 277V AC LED FLUORESCENT LUMINAIRE RED RED WHITE RED RED WHITE DIM IN VIOLET DIM IN ...

Page 4: ...ously within 5 seconds to force a 30 second monthly test After the test is complete the next 30 day monthly test will count from this date 2 Press the LTS 3 times continuously within 5 seconds to force a 90 minute annual test After the test is completed the next 52 week annual test will count from this date 3 During any manual test press and hold the LTS for greater than 3 seconds to terminate a m...