background image

 

B800 Series 

Frequency Inverter 

 

 

 
 
 
 
 

 

  BEDFORD (QUANZHOU) ELECTRONIC CO., LTD 

 

Summary of Contents for B800 Series

Page 1: ...B800 Series Frequency Inverter BEDFORD QUANZHOU ELECTRONIC CO LTD ...

Page 2: ...h may let you acquire more ideal use effects 10 7 2 Keyboard operation mode 11 7 3 Keyboard operation for FOR REV 11 7 4 Terminal control mode 13 7 5 Parameter resume ex work value 13 7 6 Saving condition after parameter modification 14 8 The symbol explanation on LCD 15 9 Parameter and data sheet 9 1 Parameter list 15 9 2 Parameter explanation 21 10 Fault diagnosis and corrective actions 10 1 Not...

Page 3: ...ER Please don t take down alter Otherwise it may cause electric shock fire and injure Don t open the cover during electrify Don t put or insert wire stick and filament etc into inverter to avoid short circuit or electric shock Please don t splash water or other liquid onto inverter NOTICE Please don t perform a withstand voltage testing to the components of inverter Absolutely don t connect output...

Page 4: ...dition which don t get damaged during transportation if damaged please don t connect with AC main power c Make sure the S N on warranty is same as inverter Please inform our salesperson ASAP if you find the above problems 3 2 Model explanation BEDFORD B800 2 001 Motor power 001 1HP 0 75KW Voltage 2 200V 4 400V Series No Brand ...

Page 5: ...4 Installation 4 1 Exterior Size 400V 1 2HP 3 5HP 7 10HP 200V 1 2HP 3 5HP 7 10HP H 165mm 214 255 W 120mm 151 180 D 123mm 160 180 ...

Page 6: ... wall mounted type Oil fog salt spray Direct sunlight Avoid use outdoors Corrosive gases or liquid Dust or metallic particles in the air Physical shock Vibration Magnetic noise Example welding machine power devices etc High humidity Radioactive materials Combustibles thinners solvents etc If few inverters are mounted into cabinet Please kindly put them on ventilated position where the good ventila...

Page 7: ...rter itself Please mount inverter onto nonflammable materials like metal and other else please don t mount it nearby nonflammable materials to avoid fire If few inverters are mounted into a controlling cabinet cooling fan must be mounted inside cabinet to ensure temperature of cabinet inside is lower than 45 to avoid overheat Please cut off AC main power prior to remove keyboard ...

Page 8: ...S N T as AC main power input terminal Single phase 220V only uses R L and S N 2 Braking resistors of single phase 220V 1hp 2hp three phase 400V 1hp 2hp are all inbuilt 3 B800 Series inverter default as keyboard control F 12 1 it will work after AC main power input ...

Page 9: ...e cooling fan of inverter would automatically start to work once the temperature reach 40 Also it would stop working when its temperature is under indoor Please attention other relevant parameter settings once braking resistor used Please don t check the signal on PCB when inverter is running Parameters have already been set when ex work please don t adjust it casually 6 Keyboard Operation 6 1 LCD...

Page 10: ... 14 to 10 and press Enter key 7 Test operation 7 1 Master some relevant functions which may help you acquire more ideal use effects Maximum and minimum output frequency F 01 F 02 The maximum and minimum speed limitations are set according to actual individual requirements Accelerate and decelerate parameter F 03 F 04 If linear acceleration time and linear deceleration time too short on some occasi...

Page 11: ...tor When F 10 0 The Speed value appears with HZ If we set F 10 as motor rated RPM which will help to improve slip compensation function under different loading conditions Low speed voltage compensation F 11 Favorable to start motor smoothly Maximum value of voltage compensation up to 25 Controlling methods select F 12 Terminal controlling method is for long distance control use Keyboard controllin...

Page 12: ... Reverse operation on Keyboard Set F 12 2 Press RUN Key 1 LCD appears to H0 0 Press key Speed increase Press RUN Key 1 again Change motor rotary direction 7 4 Terminal controlling operation mode Parameter F 12 0 Connect the start stop switcher between terminal 1 and 2 Connect one potentiometer 1KΩ 10KΩ among terminal 5 6 and 7 When Start Off switcher ON Turn potentiometer to change output frequenc...

Page 13: ...ified they would be saved in EEPROM when AC main power is cut off As F 38 1 all parameters could also be modified but they would not be saved in EEPROM when AC main power is cut off As F 38 2 all parameters couldn t be modified read only Notice To prevent other persons modify parameters causally please select any number between 0 and 9999 for parameters F 37 enter into Extended menu access passwor...

Page 14: ...r Description Range Default F 01 Maximum speed F 02 to 5 F 09 max 545Hz 50Hz F 02 Minimum speed 0 to F 01 max 545Hz 0Hz F 03 Linear Accel time s 0 1 to 3 000s 5s F 04 Linear Decel time s 0 1 to 3 000s 5s F 05 Stop mode select 0 2 linear stop ramp stop 1 inertia stop coast to stop 0 F 06 V F characteristic 0 Constant torque INDUSTRIAL 1 Pump fan HVAC 0 F 07 Rapid linear Decel time s when power cut ...

Page 15: ...ective power stage switching frequency Carrier wave frequency selection 4 8 16kHz 16 kHz F 18 Relay output function 0 Drive enabled 1 Drive healthy 2 At set speed 3 Speed zero 4 Motor at max speed F 01 1 Drive healthy F 19 Multi function contact input selection 0 to 11 0 F 20 Preset Jog speed 1 F 01 reverse to F 01 50Hz F 21 Preset Jog speed 2 F 01 reverse to F 01 0Hz F 22 Preset Jog speed 3 F 01 ...

Page 16: ... of max voltage 10 F 32 DC injection braking time 0 to 250s 0s F 33 DC injection on enable 0 Inactive 1 Enabled 0 F 34 External Brake Resistor 0 No brake resistor fitted 1 Optidrive braking resistor 2 Customer specified resistor 1 F 35 Speed reference scaling factor analog or digital F09 1 to 500 100 F 36 Drive address s comms 0 to 63 1 F 37 Access code definition 0 to 9999 10 F 38 Parameter acces...

Page 17: ...llance content Range of setting Factory setting value F 00 1 Original analog input 2 Original analog input F 35 Hz 3 Setting frequency Hz 4 Output frequency Hz 5 Slip frequency Hz 6 Stator frequency Hz 7 Motor voltage VAC 8 DC bus voltage VDC 9 Inside thermistor NTC 0 255 0 9 1 ...

Page 18: ... Speed 1 Digital Input 3 Closed Digital Input 4 Open Preset Jog Speed 2 Digital Input 3 Open Digital Input 4 Closed Preset Jog Speed 3 Digital Input 3 Closed Digital Input 4 Closed Preset Jog Speed 4 3 Open Stop disable Closed Run enable External trip input Open TRIP Closed no trip Open Analog speed reference Closed Preset Jog Speed 1 4 Open Stop disable Closed Run enable Open Run forward Closed R...

Page 19: ... Open N O Momentary close to run fwd Normally Closed N C Momentary open to Stop disable Normally Open N O Momentary close to run reverse Forward means motor rotary along clockwise direction Multi functions contact input selection F 19 set to 0 When multi function contact 4 OFF Analog input is voltage signal When multi function contact 4 ON Analog input is current signal The type of analog input si...

Page 20: ...pid linear deceleration function F 07 9 2 Parameter explanation Standard parameter group F 01 max output frequency Maximum frequency limitation Speed refer to F 10 F 02 min output frequency Minimum frequency limitation Speed refer to F 10 F 03 linear Accel time S The required time accelerate from 0 to max speed F 04 linear Decel time S The required time decelerate from max speed to 0 F 05 stop mod...

Page 21: ...re 0 curve is constant torque 1 curve is variable torque B Through adjust parameter F 26 F 29 V F curve can be further changed For example Set F 26 80 F 29 40Hz which would cause voltage V at 40HZ reduce 20 percent C The fluctuant range of voltage 1 For frequency increase Frequency is straight upward from parameter F 29 to basic frequency 2 For frequency descend Frequency is straight downward from...

Page 22: ...f the motor Changing F 09 resets F 02 F 10 F 26 F 28 to 0 F 01 F 09 F 10 motor output rated voltage When non zero Speed is displayed in RPM in parameters F 01 F 02 F 20 F 23 F 27 and F 28 Example Motor rated frequency is 50Hz Speed can be set from 600 3000RPM min when motor speed is non zero rotary speed should be shown on the unit of RPM F 11 Low speed voltage compensation Voltage boost Applies a...

Page 23: ...7 to prevent unauthorized access to the extended parameter set Extended Parameter Set F 15 Motor rated RPM When F 15 is non zero the applied motor voltage is controlled and scaled so that the specified voltage is achieved at rated frequency F 09 F 16 Input analog signal format Analog input format on terminal 6 If a current input format is set F 19 0 Multi function contact input 3 must be closed fo...

Page 24: ... greater than 5 of base frequency The drive is in overload when the motor current exceeds F 08 F 19 Multi functions contact input selection Multi functions contact 2 3 and 4 correspondence with common contact 1 to effect ON OFF functions Defines function of digital inputs See also F 16 and Multi functions contact input table F 20 F 23 multi stages speed 1 4 Refer to multi functions contact input s...

Page 25: ...ut which is step jumping digital F 26 V F Characteristic adjustment factor Used with F 29 to adjust the V F characteristic When F 26 100 motor voltage is increased When F 26 100 motor Voltage is reduced F 27 Skip frequency speed Centre point for skip frequency band The skip frequency band defined by F 27 F 28 is mirrored around zero for negative speeds ...

Page 26: ...wer up or after a clearing a trip for the drive to run When set to Auto 0 drive will run whenever digital input 1 is closed if not tripped Auto 1 4 makes 1 4 attempts to automatically restart after a trip 25s between attempts If fault has cleared drive will restart Drive must be powered down reset on the keypad or reset by re enabling the drive to reset auto reset counter When F 12 is set to 1 or ...

Page 27: ...trol terminal 6 up or down or the digital reference in keypad or Slave mode up or down see F 12 F 36 Communication address Drive address 0 means order invalid F 37 Access code definition Defines Extended Parameter Set access code F 14 F 38 Parameter access lock Controls user access to parameters When F 38 0 all parameters can be changed and these changes will be stored automatically When F 38 1 ch...

Page 28: ...Stop which means the inverter is non abnormity it s under standby Notice if terminal 1 2 always close chronically during service use F 30 should be set to Auto 0 10 2 TROUBLESHOOTING Fault Code What has happened What to do P SET Default parameters loaded Press STOP key to confirm and enter parameter values O C Over current on drive output Excess load on the motor 1 Motor at constant speed investig...

Page 29: ...p Additional space or cooling needed Hd FIt Hardware fault Refer to your BEDFORD Authorized Distributor Ai Err Current analog input out of range Check input current in range defined by F 16 OL brt Braking Resistor Overload Increase decel time F 04 or reduce braking resistor value EE FIt EEPROM fault Parameters not saved defaults reloaded Try again If problem recurs refer to your BEDFORD Authorized...

Page 30: ...olume 0 1Hz Overloading capacity Rated output 150 1 minute 175 2 seconds Frequency setting signal 0 10V 10 0V 10 10V 4 20mA 0 20mA 20 4mA 6 types of standard signals No of V F Patterns Random V F curve Location Indoor protected from corrosive gases and dust Ambient temperature 10 40 if beyond the allowable degree one degree will derogate 5 of output current Storage temperature 40 60 Environmental ...

Page 31: ...y resolution Analog input volume 0 1Hz Overloading capacity Rated output 150 1 minute 175 2 seconds Frequency setting signal 0 10V 10 0V 10 10V 4 20mA 0 20mA 20 4mA 6 types of standard signals No of V F Patterns Random V F curve Location Indoor protected from corrosive gases and dust Ambient temperature 10 40 if beyond the allowable degree one degree will derogate 5 of output current Storage tempe...

Page 32: ...AGENT 1 ...

Reviews: