710
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
■
H2-62: Terminal M1-M2 Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
H2-62
(1B48)
Expert
Terminal M1-M2 Delay
Time
Sets the minimum on time used to output the logical calculation results from terminal M1-M2.
0.1 s
(0.0 - 25.0 s)
■
H2-63: Term M3-M4 Secondary Function
No.
(Hex.)
Name
Description
Default
(Range)
H2-63
(1B49)
Expert
Terminal P1 Secondary
Function
Sets the second function for terminal M3-M4. Outputs the logical calculation results of the
terminals assigned to functions by
H2-02 [Term P1 Function Selection]
.
F
(0 - FF)
■
H2-64: Terminal M3-M4 Logical Operation
No.
(Hex.)
Name
Description
Default
(Range)
H2-64
(1B4A)
Expert
Terminal P1 Logical
Operation
Selects the logical operation for the two functions selected by
H2-02 [Term M3-M4 Function
Selection]
and
H2-63 [Term M3-M4 Secondary Function]
.
0
(0 - 8)
Note:
Refer to
Output of Logical Operation Results of MFDO on page 703
for more information about the relationship between parameter
settings and logical operations.
■
H2-65: Terminal M3-M4 Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
H2-65
(1B4B)
Expert
Terminal M3-M4 Delay
Time
Sets the minimum on time used to output the logical calculation results from terminal M3-M4.
0.1 s
(0.0 - 25.0 s)
■
H2-66: Term M5-M6 Secondary Function
No.
(Hex.)
Name
Description
Default
(Range)
H2-66
(1B4C)
Expert
Term M5-M6 Secondary
Function
Sets the second function for terminal M5-M6. Outputs the logical calculation results of the
terminals assigned to functions by
H2-03 [Term P1-C1 Function Selection]
.
F
(0 - FF)
■
H2-67: Terminal M5-M6 Logical Operation
No.
(Hex.)
Name
Description
Default
(Range)
H2-67
(1B4D)
Expert
Terminal M5-M6 Logical
Operation
Sets the logical operation for the two functions selected by
H2-03 [Terminal M5-M6 Function
Select]
and
H2-66 [Term M5-M6 Secondary Function]
.
0
(0 - 8)
Note:
Refer to
Output of Logical Operation Results of MFDO on page 703
for more information about the relationship between parameter
settings and logical operations.
■
H2-68: Terminal M5-M6 Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
H2-68
(1B4E)
Expert
Terminal P2 Minimum ON
Time
Sets the minimum on time used to output the logical calculation results from terminal M5-M6.
0.1 s
(0.0 - 25.0 s)
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...