Table 2.16 Control Circuit Output Terminals
Mode
Terminals
Name (Default)
Function (Signal Level)
Fault relay output
MA
N.O. output
(Fault)
•
Relay output
•
DC30 V, 10 mA to 1 A
•
AC250 V, 10 mA to 1 A
•
Minimum load: 5 V, 10 mA (Reference value)
MB
N.C. output
(Fault)
MC
Digital output common
Digital Outputs
M1
Digital Outputs
(Brake Release Command)
•
Relay output
•
DC30 V, 10 mA to 1 A
•
AC250 V, 10 mA to 1 A
•
Minimum load: 5 V, 10 mA (Reference value)
Note:
Switching life is estimated at 8,000,000 times (assumes 30 mA, inductive load) or 200,000
times (assumes 1 A, resistive load). When switching inductive load such as relay coils,
connect surge absorbing element in parallel against the load for effective protection of relay
contact.
M2
M3
Digital Outputs
(During run)
M4
M5
Digital Outputs
(Speed agree 1)
M6
Multi-function
photocoupler
output
P1
Multi-function photocoupler output
(Drive operation ready (READY))
•
Photocoupler output
•
48 V, 2 mA to 50 mA
Note:
Connect a flywheel diode as shown in
when driving a reactive load such as a
relay coil. Ensure the diode rating is greater than the circuit voltage.
C1
P2
Multi-function photocoupler output
(Minor Fault)
C2
A - External power, 48 V max.
B - Flywheel diode
C - Coil
D - 50 mA or less
Figure 2.106 Connecting a Flywheel Diode
Table 2.17 Control Circuit Monitor Output Terminals
Mode
Terminals
Name (Default)
Function (Signal Level)
Monitor output
FM
Analog monitor output 1
(Output frequency)
Voltage output
•
0 V to +10 V/0% to 100%
•
-10 V to +10 V/-100% to +100%
Note:
Select with
H4-07 [MFAO Term FM Signal Level Select]
or
H4-08 [MFAO Term AM Signal
Level Select]
.
AM
Analog monitor output 2
(Output current)
AC
Monitor common
0 V
■
External Power Supply Input Terminals
Refer to
for a list of the functions of the external power supply input terminals.
Table 2.18 External Power Supply Input Terminals
Type
Terminal
Name (Default)
Function
External Power Supply Input
Terminals
PS
External 24 V power supply input
Supplies backup power to the drive control circuit, keypad, and option board.
21.6 VDC to 26.4 VDC, 700 mA
AC
External 24 V power supply ground
0 V
Alarm Display When You Use External 24 V Power Supply
When you use an external 24 V power supply, the drive detects an alarm as shown in
if you set
o2-23
[External 24V Powerloss Detection]
and
o2-26 [Alarm Display at Ext. 24V Power]
for the main circuit power
supply. Set the alarm display as necessary.
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...