Note:
The lower value is enabled when both
L7-01 to L7-04
and either analog inputs or communication option torque limits set torque limits
for the same quadrant.
As in the following example of parameter settings, the torque limit for quadrant 1 is 130% and the torque limit for quadrants 2, 3, and 4
is 150%.
Settings:
L7-01
= 130%,
L7-02
,
L7-03
,
L7-04
= 200%, MFAI torque limit = 150%
■
L7-01: Forward Torque Limit
No.
(Hex.)
Name
Description
Default
(Range)
L7-01
(04A7)
RUN
Forward Torque Limit
Sets the torque limit value for forward motoring as a percentage, where motor rated torque is the
100% value.
200%
(0 - 300%)
Note:
•
Use this method to set the torque limit and enable the lower torque limit:
–
Set
H3-02
,
H3-06
, or
H3-10 = 10, 15 [MFAI Function Select = Forward, Reverse/Regenerative Torque Limit]
.
–
Use a communication option to set the torque limits
•
You must think about drive capacity when a large quantity of torque is necessary. If you set the value too high, the drive can detect
oC
[Overcurrent]
.
•
If you set the value too low with large loads, the motor can stall.
■
L7-02: Reverse Torque Limit
No.
(Hex.)
Name
Description
Default
(Range)
L7-02
(04A8)
RUN
Reverse Torque Limit
Sets the torque limit value for reversed motoring as a percentage, where motor rated torque is the
100% value.
200%
(0 - 300%)
Note:
•
Use this method to set the torque limit and enable the lower torque limit:
–
Set
H3-02
,
H3-06
, or
H3-10 = 10, 15 [MFAI Function Select = Forward, Reverse/Regenerative Torque Limit]
.
–
Use a communication option to set the torque limits
•
You must think about drive capacity when a large quantity of torque is necessary. If you set the value too high, the drive can detect
oC
[Overcurrent]
.
•
If you set the value too low with large loads, the motor can stall.
■
L7-03: Forward Regenerative Trq Limit
No.
(Hex.)
Name
Description
Default
(Range)
L7-03
(04A9)
RUN
Forward Regenerative Trq
Limit
Sets the torque limit value for forward regenerative conditions as a percentage of the motor rated
torque.
200%
(0 - 300%)
Note:
•
Use this method to set the torque limit and enable the lower torque limit:
–
Set
H3-02
,
H3-06
, or
H3-10 = 10, 15 [MFAI Function Select = Forward, Reverse/Regenerative Torque Limit]
.
–
Use a communication option to set the torque limits
•
You must think about drive capacity when a large quantity of torque is necessary. If you set the value too high, the drive can detect
oC
[Overcurrent]
.
•
If you set the value too low with large loads, the motor can stall.
■
L7-04: Reverse Regenerative Trq Limit
No.
(Hex.)
Name
Description
Default
(Range)
L7-04
(04AA)
RUN
Reverse Regenerative Trq
Limit
Sets the torque limit value for reversed regenerative conditions as a percentage of the motor rated
torque.
200%
(0 - 300%)
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...