Note:
•
If you decelerate frequently and the overexcitation time is long, the drive can detect
oL1 [Motor Overload]
faults. If the drive detects
oL1
, decrease the deceleration time or install a braking resistor to the drive.
•
The deceleration time during Overexcitation Deceleration changes when the motor characteristics and machine inertia change. Adjust
the
n3-13 [OverexcitationBraking (OEB) Gain]
and
n3-23 [Overexcitation Braking Operation]
levels. Refer to
“
n3: Overexcite
Braking
”
for more information.
5 : Overexcitation/High Flux 2
Enables Overexcitation/High Flux 2. This function decreases the possible deceleration time more than
Overexcitation/High Flux.
The drive decreases motor speed and tries to keep the DC bus voltage at the
L3-17
level.
If the drive detects
oL1
, decrease the values set in
n3-13
and
n3-21
. If the drive detects
ov
, increase the value set
in
C1-02, C1-04, C1-06, and C1-08 [Deceleration Times]
.
Note:
•
During Overexcitation/High Flux 2, the drive disables Hunting Prevention in V/f Control and also disables Speed Control that uses
torque limit in OLV Control.
•
Refer to
“
n3: Overexcite Braking
”
for more information.
■
L3-05: Stall Prevention during RUN
No.
(Hex.)
Name
Description
Default
(Range)
L3-05
(0493)
Stall Prevention during
RUN
Sets the function to enable and disable Stall Prevention During Run.
1
(0 - 2)
Stall Prevention function during run prevents the motor from stalling by automatically reducing the speed when
an
oL1 [Motor Overload]
occurs while the motor is running at constant speed.
Note:
The Stall Prevention during Run function is disabled regardless of the setting of
L3-05
and
L3-06 [Stall Prevent Level during Run]
if the
output frequency falls below 6 Hz.
0 : Disabled
Drive runs at the set frequency reference. A heavy load may cause the motor to stall and trip the drive with an
oC
[Overcurrent]
or
oL1
.
1 : Deceleration Time 1 (
C1-02
)
The drive will decelerate for the time set in
C1-02 [Deceleration Time 1]
.If the current exceeds the Stall
Prevention level set in
L3-06
. When the current level drops below
“
L3-06
setting value - 2%
”
for 100 ms, drive
accelerates again for the acceleration time valid at that time until the set frequency is reached.
2 : Deceleration Time 2 (
C1-04
)
This setting functions in the same manner as setting 1. If the Stall Prevention function is enabled, the drive
decelerates with the value set in
C1-04 [Deceleration Time 2]
.
■
L3-06: Stall Prevent Level during Run
No.
(Hex.)
Name
Description
Default
(Range)
L3-06
(0494)
Stall Prevent Level during
Run
Sets the output current level at which the Stall Prevention function is enabled during run when the
drive rated output current is 100%.
Determined by L8-38
(30 - 150%)
Note:
•
This parameter is applicable if
L3-05 = 1, 2 [Stall Prevention during RUN = Deceleration Time 1 (C1-02), Deceleration Time 2 (C1-
04)]
.
•
The upper limit of this setting is determined by
L8-38 [Carrier Frequency Reduction]
.
•
Depending on the setting of
L3-23 [Stall P Reduction at Constant HP]
the level is automatically decreased in the constant power range.
Use an Analog Input to Change the Stall Prevent Level during Run
When
H3-xx = 8 [MFAI Function Selection = Stall Prevent Level During Run]
, you can change the stall
prevention level during run through the input gain and bias settings for terminals A1, A2, and A3.
If you set the input level for terminals A1, A2, and A3
[H3-xx = 8]
and
L3-06
, the drive will use the smaller value
for Stall Prevent Level during Run.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...