Put the wiring cover in its initial position. Put the cables through the holes that you cut out of the wiring
cover.
Figure 7.77 Reattach the Wiring Cover
■
Connect the Control Circuit Terminal Block
1.
To put a wired control circuit terminal block in the drive, align it with the guides and move it straight up.
A - Guides
Figure 7.78 Put the Terminal Block into the Connector
2.
Use M3 screws to safety the terminal block.
Tighten the screws to a correct tightening torque:
• M3 screws: 0.5 N
∙
m to 0.6 N
∙
m (4.4 lbf
∙
in to 5.3 lbf
∙
in)
Figure 7.79 Safety the Terminal Block
3.
Install the front cover and the keypad to their initial positions.
4.
Check
o2-04 [Drive Model (KVA) Selection]
.
Note:
•
When you save parameter information in a keypad that you installed before you replaced the terminal block, make sure that you use
that keypad to restore the parameter data.
•
To reset the performance life monitors for the components, set
o4-01 to o4-13 [Maintenance Period]
.
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...