SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
767
As decreasing the carrier frequency increases the overload tolerance, the overload capacity is increases
temporarily for
oL2 [Drive Overloaded]
, allowing the drive to run through transient load peaks without tripping.
0 : Disabled
No carrier frequency reduction at high current.
1 : Enabled below 6 Hz
The carrier frequency is reduced at speeds below 6 Hz when the current exceeds 100% of the drive rated current.
The drive returns to the normal carrier frequency when the current falls below 88% or the output frequency
exceeds 7 Hz.
2 : Enabled for All Speeds
The carrier frequency is reduced at the following speeds:
•
Output current is at least 100% of the drive rated current while the frequency reference is lower than 6 Hz.
•
Output current is at least 112% of the drive rated current while the frequency reference is higher than or equal to
7 Hz.
The drive uses the delay time set in
L8-40 [CarrierFreqReduct Off DelayTime]
and a hysteresis of 12% when
switching the carrier frequency back to the set value.
■
L8-39: Carrier Freq Reduction during oL
No.
(Hex.)
Name
Description
Default
(Range)
L8-39
(04F0)
Carrier Freq Reduction
during oL
Sets the low carrier frequency when IGBT protection is enabled.
Determined by o2-04
(1.0 - 15.0 kHz)
Sets the low carrier frequency when IGBT protection is enabled.
■
L8-40: Carrier Freq Reduction Off-Delay
No.
(Hex.)
Name
Description
Default
(Range)
L8-40
(04F1)
Carrier Freq Reduction Off-
Delay
Sets the length of time until the automatically reduced carrier frequency returns to the condition
before the reduction.
Determined by A1-02
(0.00 - 2.00 s)
Set
L8-40 ≠ 0.00
to enable the carrier frequency reduction function during start-up. When operation starts, the
drive automatically decreases the carrier frequency. When the time set in
L8-40
is expired, the carrier frequency
returns to the value set in
C6-02 [Carrier Frequency Selection]
.
■
L8-41: High Current Alarm Selection
No.
(Hex.)
Name
Description
Default
(Range)
L8-41
(04F2)
High Current Alarm
Selection
Triggers an
HCA [Current Alarm]
when the output current exceeds 150% of the drive rated
current.
1
(0, 1)
0 : Disabled
An
HCA
is not detected.
1 : Enabled
An
HCA
is triggered when the output current exceeds 150% of the drive rated current.
The MFDO terminal set for Alarm
[H2-01 to H2-05 = 10]
turns ON.
■
L8-55: Internal DB TransistorProtection
No.
(Hex.)
Name
Description
Default
(Range)
L8-55
(045F)
Internal DB
TransistorProtection
Sets the protection function for the internal braking transistor.
1
(0, 1)
0 : Disable
Disables braking transistor protection.
Use this setting in the following situation. Enabling the braking transistor in the following situations may cause an
rF [Braking Resistor Fault]
.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...