YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
507
Setting Value
Function
Description
Ref.
E
Fault
The terminal activates when the drive detects a fault.
Note:
The terminal will not activate for
CPF00
and
CPF01 [Control Circuit Error]
faults.
F
Not Used
Use this setting for unused terminals or to use terminals in through mode. Also use this setting as the PLC contact
output via MEMOBUS/Modbus or the communication option. This signal does not function if you do not
configure signals from the PLC.
10
Alarm
The terminal activates when the drive detects a minor fault.
11
Fault Reset Command
Active
The terminal activates when the drive receives the Reset command from the control circuit terminal, serial
communications, or the communication option.
13
Speed Agree 2
The terminal activates when the output frequency is in the range of the frequency reference ±
L4-04 [Speed Agree
Detection Width(+/-)]
.
Note:
In CLV, the motor speed is the reference.
ON : The output frequency is in the range of
“
frequency reference ±
L4-04
”
.
OFF : The output frequency is not in the range of
“
frequency reference ±
L4-04
”
.
14
User-Set Speed Agree 2
The terminal activates when the output frequency is in the range of
L4-03 [Speed Agree Detection Level (+/-)]
±
L4-04 [Speed Agree Detection Width (+/-)]
and in the range of the frequency reference ±
L4-04
.
ON : The output frequency is in the range of
“
L4-03
±
L4-04
”
and the range of frequency reference ±
L4-04
.
OFF : The output frequency is not in the range of
“
L4-03
±
L4-04
”
nor the range of frequency reference ±
L4-04
.
15
Frequency Detection 3
The terminal deactivates when the output frequency >
“
L4-03 [Speed Agree Detection Level(+/-)]
+
L4-04 [Speed
Agree Detection Width(+/-)]
”
. After the terminal deactivates, the terminal stays deactivated until the output
frequency is at the value of
L4-03
.
Note:
•
The detection level configured with
L4-03
is a signed value. Detections only occur one specific orientation.
•
In CLV, the motor speed is the reference.
ON : The output frequency <
L4-03
, or the output frequency ≤
“
L4-03
+ L4-04
”
OFF : The output frequency is higher than
L4-03
+
L4-04
.
16
Frequency Detection 4
The terminal activates when the output frequency >
L4-03 [Speed Agree Detection Level(+/-)]
. After the terminal
activates, the terminal stays activated until the output frequency =
“
L4-03
-
L4-04
”
.
Note:
•
The detection level set in
L4-03
is a signed value. The drive will only detect in one direction.
•
The drive outputs the motor speed status when
A1-02 = 3 [Control Method Selection = CLV]
.
ON : The output frequency >
L4-03
OFF : The output frequency <
“
L4-03
-
L4-04
”
, or the output frequency ≤
L4-03
17
Torque Detection 1 (N.
C.)
The terminal deactivates when the drive detects overtorque.
OFF : The output current/torque >
L6-02 [Torque Detection Level 1]
for longer than the time set in
L6-03 [Torque
Detection Time 1]
.
18
Torque Detection 2 (N.
O.)
The terminal activates when the drive detects overtorque.
ON : The output current/torque >
L6-05 [Torque Detection Level 2]
for longer than the time set in
L6-06 [Torque
Detection Time 2]
.
19
Torque Detection 2 (N.
C.)
The terminal deactivates when the drive detects overtorque.
OFF : The output current/torque >
L6-05 [Torque Detection Level 2]
for longer than the time set in
L6-06 [Torque
Detection Time 2]
.
1A
During Reverse
The terminal activates when the motor operates in the reverse direction.
ON : The motor is operating in the reverse direction.
OFF : The motor is operating in the forward direction or the motor stopped.
1B
During Baseblock (N.C.)
The terminal deactivates during baseblock. When the drive is in baseblock, the drive output transistor stops
switching and does not make DC bus voltage.
ON : The drive is not in baseblock.
OFF : During baseblock
1C
Motor 2 Selected
The terminal activates when you select motor 2.
ON : Motor 2 Selected
OFF : Motor 1 Selected
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...