This function is used to completely stop a motor with a large inertia during deceleration, and prevent the inertia
from causing the motor to continue rotating.
A setting of 0.00 disables this function.
When a longer time is necessary to stop the motor, increase the value.
■
b2-08: Magnetic Flux Compensation Value
No.
(Hex.)
Name
Description
Default
(Range)
b2-08
(0190)
Magnetic Flux
Compensation Value
Sets how much current the drive injects when DC Injection Braking at Start starts (Initial
Excitation) as a percentage of
E2-03 [Motor No-Load Current]
.
0%
(0 - 1000%)
This parameter is effective when you start a high-capacity motor (a motor with a large secondary circuit time
constant). This function can quickly increase motor flux to make high starting torque (a process called initial
excitation).
The current level for DC Injection Braking at start changes linearly from the setting of
b2-08
to the setting of
b2-
03
as shown in
Figure 11.24 DC Current Level during DC Injection Braking at Start
Note:
•
If
b2-08 < 100%
, flux will develop very slowly.
•
When
b2-08 = 0%
, the DC current level will be the DC Injection current set in
b2-02 [DC Injection Braking Current]
.
•
If
b2-08
is set too high, DC Injection Braking at start can cause a large noise. Adjust
b2-08
to decrease the volume to the permitted
level.
◆
b4: Timer Function
The drive uses timers to delay activating and deactivating MFDO terminals.
Timers prevent chattering noise from sensors and switches.
Set delay times in parameters
b4-03 to b4-12
to enable this function.
■
Timer Function Operation
•
Setting ON/OFF-Delay Time for MFDO
The following diagram shows an example of how the timer function works using H2-01 terminals. Set this
function with
b4-03 [Terminal M1-M2 ON-Delay Time]
and
b4-04 [Terminal M1-M2 OFF-Delay Time]
.
Figure 11.25 Example of How the Timer Function Works with H2-01 Terminals
Note:
When the terminal is triggered, it continues for a minimum of 100 ms regardless of the setting of on/off-delay time of MFDO terminal.
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...