708
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
■
H2-32: Comparator 1 Filter Time
No.
(Hex.)
Name
Description
Default
(Range)
H2-32
(159A)
Comparator 1 Filter Time
Sets the time constant that is applied to the primary delay filter used for the analog output of the
monitor selected with
H2-20 [Comparator 1 Monitor Selection]
.
0.0s
(0.0 - 10.0 s)
Note:
For information on the comparator function, refer to
and
■
H2-33: Comparator1 Protection Selection
No.
(Hex.)
Name
Description
Default
(Range)
H2-33
(159B)
Comparator1 Protection
Selection
Selects the operation of the drive when it detects
CP1 [Comparator1 Limit Fault]
.
4
(0 - 4)
0 : Ramp to Stop
The drive ramps the motor to stop according to the deceleration time. Fault relay output terminal MA-MC will
turn ON, and MB-MC will turn OFF.
1 : Coast to Stop
The drive output shuts off and the motor coasts to stop. Fault relay output terminal MA-MC will turn ON, and
MB-MC will turn OFF.
2 : Fast Stop (Use C1-09)
The drive stops the motor using the deceleration time set in
C1-09 [Fast Stop Time]
. Fault relay output terminal
MA-MC will turn ON, and MB-MC will turn OFF.
3 : Alarm Only
The keypad shows
CP1
, and the drive continues operation. The output terminal set for
Alarm [H2-01 to H2-05 =
10]
switches ON.
4 : Operate at Reduced Speed (L8-19)
■
H2-34: Comparator 2 Filter Time
No.
(Hex.)
Name
Description
Default
(Range)
H2-34
(159C)
Comparator 2 Filter Time
Sets the time constant that is applied to the primary delay filter used for the analog output of the
monitor selected with
H2-26 [Comparator 2 Monitor Selection]
.
0.0s
(0.0 - 10.0 s)
■
H2-35: Comparator2 Protection Selection
No.
(Hex.)
Name
Description
Default
(Range)
H2-35
(159D)
Comparator2 Protection
Selection
Selects the operation of the drive when
CP2 [Comparator2 Limit Fault]
is detected.
4
(0 - 4)
0 : Ramp to Stop
The drive ramps the motor to stop according to the deceleration time. Fault relay output terminal MA-MC will
turn ON, and MB-MC will turn OFF.
1 : Coast to Stop
The drive output shuts off and the motor coasts to stop. Fault relay output terminal MA-MC will turn ON, and
MB-MC will turn OFF.
2 : Fast Stop (Use C1-09)
The drive stops the motor using the deceleration time set in
C1-09 [Fast Stop Time]
. Fault relay output terminal
MA-MC will turn ON, and MB-MC will turn OFF.
3 : Alarm Only
The keypad shows
CP2
, and the drive continues operation. The output terminal set for
Alarm [H2-01 to H2-05 =
10]
switches ON.
4 : Operate at Reduced Speed (L8-19)
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...