YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
639
This pattern is used to rotate motors at greater than 60 Hz. Output voltage is constant when operating at greater
than 60 Hz.
Note:
The voltage values in the figure represent those when using 200 V class drives. Double the values for 400 V class drives.
2003 - 2018, 4002 - 4009
2025 - 2180, 4015 - 4091
2215 - 2415, 4112 - 4605
F : Custom
Enables a custom V/f pattern by changing
E1-04 to E1-13 [V/f Pattern for Motor 1]
.
The default settings are equivalent to setting value
1 [Const Trq, 60Hz base, 60Hz max]
.
■
E1-04: Maximum Output Frequency
No.
(Hex.)
Name
Description
Default
(Range)
E1-04
(0303)
Maximum Output
Frequency
Sets the maximum output frequency for the V/f pattern.
Determined by A1-02
(Determined by A1-02)
■
E1-05: Maximum Output Voltage
No.
(Hex.)
Name
Description
Default
(Range)
E1-05
(0304)
Maximum Output Voltage
Sets the maximum output voltage for the V/f pattern.
200.0
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
■
E1-06: Base Frequency
No.
(Hex.)
Name
Description
Default
(Range)
E1-06
(0305)
Base Frequency
Sets the base frequency for the V/f pattern.
Determined by A1-02
(0.0 - E1-04)
■
E1-07: Mid Point A Frequency
No.
(Hex.)
Name
Description
Default
(Range)
E1-07
(0306)
Mid Point A Frequency
Sets a middle output frequency for the V/f pattern.
Determined by A1-02
(0.0 - E1-04)
■
E1-08: Mid Point A Voltage
No.
(Hex.)
Name
Description
Default
(Range)
E1-08
(0307)
Mid Point AVoltage
Sets a middle output voltage for the V/f pattern.
Determined by A1-02
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
Note:
Default setting is determined by
A1-02 [Control Method Selection]
and
o2-04 [Drive Model (KVA) Selection]
.
■
E1-09: Minimum Output Frequency
No.
(Hex.)
Name
Description
Default
(Range)
E1-09
(0308)
Minimum Output
Frequency
Sets the minimum output frequency for the V/f pattern.
Determined by A1-02
(Determined by A1-02 and
E1-04)
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...