YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
713
Figure 11.61 Speed Agree 1 Time Chart
ON : The output frequency is in the range of “frequency reference
±
L4-02
”.
OFF : The output frequency does not align with the frequency reference although the drive is
running.
■
3: User-Set Speed Agree 1
Setting Value
Function
Description
3
User-Set Speed Agree 1
The terminal activates when the output frequency is in the range of
L4-01 [Speed Agree Detection Level]
±
L4-02 [Speed Agree
Detection Width]
and in the range of the frequency reference ±
L4-02
.
Note:
•
The detection function operates in the two motor rotation directions. The drive uses the
L4-01
value as the forward/reverse detection
level.
•
The drive outputs the motor speed status when
A1-02 = 3 [Control Method Selection = CLV]
. The drive outputs the motor speed status
when
A1-02 = 4 [Control Method Selection = AOLV]
and
n4-72 = 1 [Speed Feedback Mode = With Encoder]
.
ON : The output frequency is in the range of “
L4-01
±
L4-02
” and the range of frequency
reference
±
L4-02
.
OFF : The output frequency is not in the range of “
L4-01
±
L4-02
” nor the range of frequency
reference
±
L4-02
.
Figure 11.62 User-Defined Speed Agree 1 Time Chart
■
4: Frequency Detection 1
Setting Value
Function
Description
4
Frequency Detection 1
The terminal deactivates when the output frequency >
“
L4-01 [Speed Agree Detection Level]
+
L4-02 [Speed Agree Detection
Width]
”
. After the terminal deactivates, the terminal stays deactivated until the output frequency is at the value of
L4-01
.
Note:
•
The detection function operates in the two motor rotation directions. The drive uses the
L4-01
value as the forward/reverse detection
level.
•
The drive outputs the motor speed status when
A1-02 = 3 [Control Method Selection = CLV]
. The drive outputs the motor speed status
when
A1-02 = 4 [Control Method Selection = AOLV]
and
n4-72 = 1 [Speed Feedback Mode = With Encoder]
.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...