676
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
5 : PPO (bit0, Enter)
This function operates when bit 0 and bit 4 in the register STW have values of 1 (operate). Refer to the
PROFIBUS-DP communication manual for more information.
■
F6-35: CANopen Node ID Selection
No.
(Hex.)
Name
Description
Default
(Range)
F6-35
(03D0)
CANopen Node ID
Selection
Sets the node address for CANopen communication. Restart the drive after you change the
parameter setting.
0
(0 - 126)
Note:
Be sure to set an address that is different than all other node addresses. Do not set this parameter to
0
. Incorrect parameter settings will
cause
AEr [Station Address Setting Error]
errors and the L.ERR LED on the option will come on.
■
F6-36: CANopen Communication Speed
No.
(Hex.)
Name
Description
Default
(Range)
F6-36
(03D1)
CANopen Communication
Speed
Sets the CANopen communications speed. Restart the drive after you change this parameter
setting.
0
(0 - 8)
0 : Auto-detection
The drive detects the network communication speed and automatically adjusts the communications speed.
1 : 10 kbps
2 : 20 kbps
3 : 50 kbps
4 : 125 kbps
5 : 250 kbps
6 : 500 kbps
7 : 800 kbps
8 : 1 Mbps
■
F6-50: DeviceNet MAC Address
No.
(Hex.)
Name
Description
Default
(Range)
F6-50
(03C1)
DeviceNet MAC Address
Sets the MAC address for DeviceNet communication. Restart the drive after you change this
parameter setting.
0
(0 - 64)
Note:
Set a MAC address that does not overlap with other nodes. Do not set this parameter to a value of 0. If the parameter is set incorrectly,
the ERR on the option card flashes, and the drive will detect the
AEr [Station Address Setting Error]
.
■
F6-51: DeviceNet Baud Rate
No.
(Hex.)
Name
Description
Default
(Range)
F6-51
(03C2)
DeviceNet Baud Rate
Sets the DeviceNet communications speed. Restart the drive after you change this parameter
setting.
0
(0 - 4)
0 : 125 kbps
1 : 250 kbps
2 : 500 kbps
3 : Adjustable from Network
The controller sets the communications speed.
4 : Detect Automatically
The drive detects the network communication speed and automatically adjusts the communications speed
accordingly.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...