490
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
F3-24
(0BF1)
Expert
Terminal DE Function
Selection
Sets the function for terminal DE of the DI-A3 when
F3-01 = 8 [Digital Input Function
Selection = Multi-Function Digital Input]
.
F
(0 - 1FF)
F3-25
(0BF2)
Expert
Terminal DF Function
Selection
Sets the function for terminal DF of the DI-A3 when
F3-01 = 8 [Digital Input Function
Selection = Multi-Function Digital Input]
.
F
(0 - 1FF)
◆
F4: Analog Output Option
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
F4-01
(0391)
Terminal V1 Function
Selection
Sets the monitor signal output from terminal V1.
Set the
x-xx
part of the
Ux-xx [Monitor]
. For example, set
F4-01 = 102
to monitor
U1-
02 [Output Frequency]
.
102
(000 - 999)
F4-02
(0392)
RUN
Terminal V1 Gain
Sets the gain of the monitor signal that is sent from terminal V1. Sets the analog signal
output level from the terminal V1 at 10 Vor 20 mA as 100% when an output for
monitoring items is 100%.
100.0%
(-999.9 - +999.9%)
F4-03
(0393)
Terminal V2 Function
Selection
Sets the monitor signal output from terminal V2.
Set the
x-xx
part of the
Ux-xx [Monitor]
. For example, set
F4-03 = 103
to monitor
U1-
03 [Output Current]
.
103
(000 - 999)
F4-04
(0394)
RUN
Terminal V2 Gain
Sets the gain of the monitor signal that is sent from terminal V2. Sets the analog signal
output level from terminal V2 at 10 Vor 20 mA as 100% when an output for monitoring
items is 100%.
50.0%
(-999.9 - +999.9%)
F4-05
(0395)
RUN
Terminal V1 Bias
Sets the bias of the monitor signal that is sent from terminal V1. When an output for
monitoring items is 0%, this parameter sets the analog signal output level from the V1
terminal as a percentage of 10 Vor 20 mA.
0.0%
(-999.9 - +999.9%)
F4-06
(0396)
RUN
Terminal V2 Bias
Sets the bias of the monitor signal that is sent from terminal V2. Set the level of the
analog signal sent from the V2 terminal at 10 Vor 20 mA as 100% when an output for
monitoring items is 0%.
0.0%
(-999.9 - +999.9%)
F4-07
(0397)
Terminal V1 Signal
Level
Sets the output signal level for terminal V1.
0 : 0 to 10 V
1 : -10 to 10 V
0
(0, 1)
F4-08
(0398)
Terminal V2 Signal
Level
Sets the output signal level for terminal V2.
0 : 0 to 10 V
1 : -10 to 10 V
0
(0, 1)
◆
F5: Digital Output Option
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
F5-01
(0399)
Terminal P1-PC
Function Select
Sets the function of terminal P1-PC on the DO-A3 option. Set
F5-09 = 2 [DO-A3
Output Mode Selection = Programmable (F5-01 to F5-08)]
to enable this function.
0
(0 - 1FF)
F5-02
(039A)
Terminal P2-PC
Function Select
Sets the function of terminal P2-PC on the DO-A3 option. Set
F5-09 = 2 [DO-A3
Output Mode Selection = Programmable (F5-01 to F5-08)]
to enable this function.
1
(0 - 1FF)
F5-03
(039B)
Terminal P3-PC
Function Select
Sets the function of terminal P3-PC on the DO-A3 option. Set
F5-09 = 2 [DO-A3
Output Mode Selection = Programmable (F5-01 to F5-08)]
to enable this function.
2
(0 - 1FF)
F5-04
(039C)
Terminal P4-PC
Function Select
Sets the function of terminal P4-PC on the DO-A3 option. Set
F5-09 = 2 [DO-A3
Output Mode Selection = Programmable (F5-01 to F5-08)]
to enable this function.
4
(0 - 1FF)
F5-05
(039D)
Terminal P5-PC
Function Select
Sets the function of terminal P5-PC on the DO-A3 option. Set
F5-09 = 2 [DO-A3
Output Mode Selection = Programmable (F5-01 to F5-08)]
to enable this function.
6
(0 - 1FF)
F5-06
(039E)
Terminal P6-PC
Function Select
Sets the function of terminal P6-PC on the DO-A3 option. Set
F5-09 = 2 [DO-A3
Output Mode Selection = Programmable (F5-01 to F5-08)]
to enable this function.
37
(0 - 1FF)
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...