H5-05: Comm Fault Detection Selection
No.
(Hex.)
Name
Description
Default
(Range)
H5-05
(0429)
Comm Fault Detection
Selection
Sets the function that detects
CE [Modbus Communication Error]
issues during MEMOBUS/
Modbus communications.
1
(0, 1)
If the drive does not receive data from the master during the time set in
H5-09 [CE Detection Time]
, it will detect
a
CE
error.
0 : Disabled
Does not detect
CE
. The drive continues operation.
1 : Enabled
Detects
CE
. If the drive detects
CE
, it will operate as specified by the setting of
H5-04 [Communication Error
Stop Method]
.
■
H5-06: Drive Transmit Wait Time
No.
(Hex.)
Name
Description
Default
(Range)
H5-06
(042A)
Drive Transmit Wait Time
Sets the time to wait to send a response message after the drive receives a command message
from the master.
5 ms
(0 - 65 ms)
Figure 11.82 Drive Transmit Wait Time
■
H5-09: CE Detection Time
No.
(Hex.)
Name
Description
Default
(Range)
H5-09
(0435)
CE Detection Time
Sets the detection time for
CE [Modbus Communication Error]
issues when communication
stops.
2.0 s
(0.0 - 10.0 s)
■
H5-10: Modbus Register 0025H Unit Sel
No.
(Hex.)
Name
Description
Default
(Range)
H5-10
(0436)
Modbus Register 0025H
Unit Sel
Sets the unit of measure used for the MEMOBUS/Modbus communications monitor register
0025H (output voltage reference monitor).
0
(0, 1)
0 : 0.1 V units
1 : 1 V units
■
H5-11: Comm ENTER Command Mode
No.
(Hex.)
Name
Description
Default
(Range)
H5-11
(043C)
Comm ENTER Command
Mode
Sets the function to make the Enter command necessary to change parameters through
MEMOBUS/Modbus communications.
0
(0, 1)
0 : ENTER Command Required
You must use the Enter command to enable changes to parameters. Make all parameter changes then input the
Enter command.
1 : ENTER Command Not Required
It is not necessary to input the Enter command to change parameters.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...