2.23 Protect the Drive during Failures
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
133
Drive Model
The maximum applicable motor
output
kW (HP)
Input Current Rating
A
Semiconductor Protection Fuse
Rated Current
Manufacturer: EATON/Bussmann
4005
1.5 (2)
4.7
FWH-50B
4006
2.2 (3)
6.7
FWH-60B
4007
3 (4)
8.9
FWH-60B
4009
4.0 (5.3)
11.7
FWH-60B
4015
5.5 (7.5)
15.8
FWH-80B
4018
7.5 (10)
21.2
FWH-90B
4024
11 (15)
30.6
FWH-150B
4031
15 (20)
41.3
FWH-200B
4039
18.5 (25)
50.5
FWH-200B
4045
22 (30)
43.1
FWH-225A
4060
30 (40)
58.3
FWH-250A
4075
37 (50)
71.5
FWH-275A
4091
45 (60)
86.5
FWH-275A
4112
55 (75)
105
FWH-300A
4150
75 (100)
142
FWH-325A
FWH-400A
4180
90 (125)
170
FWH-500A
4216
110 (150)
207
FWH-600A
4260
132 (175)
248
FWH-700A
4304
160 (200)
300
FWH-800A
4371
200 (250)
373
FWH-1000B
4414
220 (300)
410
FWH-1200B
4453
250 (335)
465
FWH-1200B
4605
315 (400)
584
FWH-1400A
FWH-1600A
*1
Yaskawa recommends a fuse with a large rated current for applications with repeated loads.
*2
Approval pending. Contact Yaskawa or your nearest sales representative.
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...