YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
351
Code
Name
Causes
Possible Solutions
oFA39
Drive Receive Time Over 3
A fault occurred in the option card.
1. De-energize the drive.
2. Make sure that the option card is correctly connected to the
connector.
3. If the problem continues, replace the option card.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
oFA40
CtrlResSel 1Err
A fault occurred in the option card.
1. De-energize the drive.
2. Make sure that the option card is correctly connected to the
connector.
3. If the problem continues, replace the option card.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
oFA41
Drive Receive Time Over 4
A fault occurred in the option card.
1. De-energize the drive.
2. Make sure that the option card is correctly connected to the
connector.
3. If the problem continues, replace the option card.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
oFA42
CtrlResSel 2Err
A fault occurred in the option card.
1. De-energize the drive.
2. Make sure that the option card is correctly connected to the
connector.
3. If the problem continues, replace the option card.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
oFA43
Drive Receive Time Over 5
A fault occurred in the option card.
1. De-energize the drive.
2. Make sure that the option card is correctly connected to the
connector.
3. If the problem continues, replace the option card.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
oFb00
Option Not Compatible with Port
The option connected to connector CN5-B is not
compatible.
Connect the option to the correct connector.
Note:
DO-A3, AO-A3, PG-B3, and PG-X3 options can connect to
connector CN5-B. To connect only one PG option card, use
the CN5-C connector.
Note:
•
Do a Fault Reset to clear the fault.
•
Fault trace is not available for these faults.
Code
Name
Causes
Possible Solutions
oFb01
Option Fault/Connection Error
The option card connected to connector CN5-B was
changed during operation.
1. De-energize the drive.
2. Refer to the option card manual and correctly connect the
option card to the connector on the drive.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
oFb02
Duplicate Options
The same option cards or the same type of option
cards are connected to connectors CN5-A, B, and C.
Connect the option card to the correct connector.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
oFb03
Diagnostic Error
A fault occurred in the option card.
1. De-energize the drive.
2. Make sure that the option card is correctly connected to the
connector.
3. If the problem continues, replace the option card.
Note:
Do a Fault Reset to clear the fault.
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...